Honeywell VRX180 User Manual

Page 16

Advertising
background image

Introduction

Video recorder – User Manual

2

1.2 Specifications

Table 1-1 Specifications

Physical

Enclosure

Metal case and rugged die cast aluminium door and frame. High impact resistant
polycarbonate keypad and glass or polycarbonate window. IP55 rating (NEMA 3) from front
panel.

Mounting (Panel)

40 mm thickness (max.) (1,57")

Dimensions

Compact size: 320 mm (12.60") depth
310 mm front face height x 317 mm width (12.21" x 12.48")
278 mm x 278 mm (10.95" x 10.95") cutout

Weight

14 kg, depending on configuration (30 lbs)

I/O Ports Standard

PC keyboard Connector (6 pin mini DIN type) - on front panel. May be used to connect to a
QWERTY keyboard or to an ASCII Barcode Reader.

Environmental

Temperature

Operating: 5 to 40°C (41 to104°F).
Storage: -20 to 60°C (-4 to 158°F).
Relative Humidity: 10 to 90%, non-condensing at 40°C.

Altitude

< 2000 meters

Installation
Category

II

Pollution Degree

2

Power

Universal power supply, 100 to 240 Vac/dc, 100 VA max.

Fuse Rating

3.15 Amps, 250 Vac slow blow

Attributes

Display

Type: Color LCD active matrix.
Screen Size: 10.4" diagonal.
Resolution: 640 x 480 pixels.
Update Rate: 1 second.
Trend Timebase: 5 min. to 24 hrs/screen; 0.5 cm/hr to 154 cm/hr vertical (0.2"/hr to 61"/hr
vertical), 0.8 cm/hr to 250 cm/hr horizontal (0.3"/hr to 100"/hr horizontal).

Keys 16

membrane

switches.

Data Archiving

Media: 100MB ZIP disk drive.
Data Types: Analog points, calculations, discrete status, alarms, diagnostics.
Trends: 4 max. (up to 12 points max. per trend)
Unit Data: 1 (up to 12 points, 10,000 records)
Alarm History: Up to 1600 records
Event History: Up to 1600 records
Diagnostic History: Up to 1600 records
Setpoint Programs: 224 maximum on LS120 floppy disk.
Storage Rate Range: 0.25 to 3600 sec.
Capacity: Automatically calculates storage time based on storage rate.

Setpoint
programmers

Up to 4

Advertising