Chapter 3 Operation

3.3 Starting the Controller 3.3.1

Turning on the Power

144

3.3 Starting the Controller

3.3.1 Turning on the Power

Turn on the controller power.

Power on procedure

The following procedure is applied for cases where the parameters are the same as those

at delivery, and the unit is not in the error occurrence mode or emergency stop mode.

Also, the number allocation for the I/O ports is shown as the same as the delivery in this

description.

[1] After confirming that the wiring is conducted correctly, supply 24V DC for brake release

as long as there is one axis or more that is equipped with a brake. If PIOs are used, also

turn on the 24-VDC PIO power.

(In the case that it is not used, the power supply is not

required, but, unless the parameter No. 11 and No. 12 have been set to “Unmonitored”,

an error might occur).

[2] Turn on the 200-VAC control power.

[3] Once the controller has started successfully (CPU has started), I/O port 301 turns ON

along with the RDY signal (system I/O). If the controller is of S/SX/SXD type, the SDN

signal (system I/O) also turns ON.

[4] Turn on the drive power.

With an R-type controller, turn on the drive power simultaneously when the control

power is turned on in [2].

With an S-type controller, turn on the drive power after the SDN signal has turned ON.

Whether the drive power is input is determined 2 sec after the RDY signal turns ON.

A timing chart of the above operation is shown below.

2sec

No error

No error

No error

No error

No error

Brake release power

I/O power

200-VAC control power

Successful start of CPU

I/O output signal port No. 301

Ready output

RDY(system I/O)

SDN

(system I/O for QAR type)
EMG1(system I/O)

EMG2(system I/O for S type)

ENB1(system I/O)

ENB2(system I/O for S type)

Secret level eror

Message level error

Operation-cancellation level error

Cold-start level error

System-shutdown level error

200-VAC drive power

● With a QAR-type controller, turn on the drive power after SDN has turned ON.

● With a PAR-type controller, turn on the control power and drive power

simultaneously.