background image

Chapter 6 Parameter

6.7 Other Parameters (All types)

379

6.7 Other Parameters (All types)

No.

Parameter name

Default

value

(reference)

Input range

Unit

Remarks

1

Auto-start program number

0

0 to 128

(Invalid if “0” is set)

2

I/O processing program

number at

operation/program abort

0

0 to 128

The start trigger is determined from the “I/O

processing program start type at operation/program

abort.”

(Note: This program will be started before

confirming an abort of other programs.)

(Invalid if “0” is set)

*

If the setting is valid, the number of user program

tasks that can be used will decrease by 1.

3

I/O processing program

number at all operation

pause

0

0 to 128

This program will be started when an

all-operation-pause command is issued due to an

all-operation-pause factor. (Only when a program is

running)

(Invalid if “0” is set)

*

If the setting is valid, the number of user program

tasks that can be used will decrease by 1.

4

Program abort type at error

0

0 to 5

0: Cancel only the program in which an error of

operation-cancellation level or higher has

generated. (If the error requires the drive source

to be cut off or a servo-OFF or all-axis

servo-OFF request to be issued, all programs

other than the “I/O processing program at

operation/program abort” will be cancelled.)

1: Cancel all programs other than the “I/O

processing program at operation/program abort”

when an error of operation-cancellation level or

higher has generated.

5

I/O processing program

start type at

operation/program abort

0

0 to 5

0: When all-operation-cancellation factor has

generated (Only when a program is running)

1: When all-operation-cancellation factor has

generated (Always)

2: All-operation-cancellation factor + Error of

operation-cancellation level or higher (“Other

parameter No. 4 = 0” is considered) (Only when

a program is running)

3: All-operation-cancellation factor + Error of

operation-cancellation level or higher (“Other

parameter No. 4 = 0” is considered) (Always)

6

PC/TP reconnection delay

at software reset

14000

1 to 99999

msec

* The setting will become effective after the

controller, PC or TP is restarted.

7

(For expansion)

0

8

(For expansion)

0

9

Reserved by the system

(change is prohibited)

0

0 to 9

10 Emergency-stop recovery

type

0

0 to 4

0: Abort operations/programs

1: Recovery after reset

2: Operation continued (Only during automatic

operation.

* Operation commands from the PC software/TP

will be aborted on the PC software/TP side.)

3: Abort operations/programs (Software reset when

the emergency stop is reset. The home-return

completion status of incremental-encoder axes

will be reset (EG approximation swap).)

4: Abort operations/programs (Error reset (only with

an error of operation-cancellation level or lower)

and auto-start program start (only if AUTO mode

AND I/O parameter No. 33 = 1 AND I/O

parameter No. 44 � 1 AND

all-operation-cancellation factor is not present)

when the emergency stop is reset). There must

be a minimum interval of 1 second after an

emergency stop is actuated before it is reset.