2 parameter usage and selection, Parameter usage and selection -4, Important – Yokogawa EJX440A User Manual

Page 14

Advertising
background image

<3. Operation>

3-4

IM 01C25T01-01E

3.2 Parameter Usage and

Selection

Before setting a parameter, please see the following

table for a summary of how and when each

parameter is used.

Table 3.2.1 Parameter Usage and Selection

Item

HART

communicator

Description

Page

Memory

Tag

Tag number, up to 8 characters

P.3-8

Descriptor

Up to 16 characters

P.3-8

Message

Up to 32 characters

P.3-8

Date

xx/yy/zz

P.3-8

Transmitter

Unit

Unit

Sets a pressure unit for the measured pressure

P.3-8

Range

LRV/URV

Sets the calibration range by the keypad

P.3-9

Apply values

Range for 4 to 20 mA DC signal is set with actual input applied

P.3-10

Output mode

Xfer fnctn

Sets mode for output signal to “linear mode” (proportional to

input differential pressure) or to “Square root mode” (proportional

to flow)

P.3-10

Damping time

constant

Pres Damp

Adjust the output response speed for the input pressure of

differential pressure

P.3-11

Output signal low cut

mode

Low Cut

Used mainly to stabilize output near 0 if output signal is the

square root mode. Two modes are available: forcing output to

0% for input below a specific value, or changing to proportional

output for input below a specific value

P.3-11

Low cut mode

Linear or Zero

P.3-11

Bi-directional flow

measurement mode

Bi-dir mode

Used to measure bi-directional flows

P.3-12

Unit for displayed

temperature

Temp Unit

Sets a temperature unit displayed on HART communicator

P.3-15

Unit for displayed

static pressure

SP Unit

Sets a pressure unit for the static pressure displayed on HART

communicator

P.3-16

Impulse line

connection

orientation

H/L Swap

Used where installation conditions make it imperative to

connect high pressure side impulse line to low pressure side of

transmitter

P.3-12

Display

Integral indicator

display mode

Disp Pres % fnctn

Sets mode for integral indicator to “linear mode” (proportional to

input differential pressure) or to “Square root mode” (proportional

to flow)

P.3-13

Disp select

Sets the following 5 types of integral indicator scale ranges

and unit: input pressure, % of range, user set scale, input static

pressure, % of static pressure range, and alternating among any

four of the above

P.3-14

Integral indicator

scale

Engr disp range

Sets Engr Unit/Modify Engr Unit/Engr LRV/Engr URV/Engr

point/Engr exp

P.3-13

Burst mode

Burst option

Selection of the data to be sent continuously (PV, % range/

current, or Process vars/crnt)

P.3-22

Burst mode

ON/OFF switching of burst mode

P.3-22

Process alarm

Process Alerts

Used for alarm generation on the integral indicator

P.3-27

HART output Multidrop mode

Poll addr

Sets the polling address (1 to 15)

P.3-22

Polling

ON/OFF switching of multidrop mode

P.3-23

IMPORTANT

After setting and sending data with the HART

communicator, wait 30 seconds before turning

off the transmitter. If it is turned off too soon, the

settings will not be stored in the transmitter.