3.4.3 Range Change

The range values are factory-set as specified by

the customer. To change the range, follow the steps

below.
(1) Keypad input — LRV and URV

• The measurement span is determined by the

upper and lower range values. In this method,

the upper and lower range values can be set

independently, and the span changes according

to the range limit values sent to the transmitter.

1

F0310.ai

EJX:YOKOGAWA

Keypad input

1 LRV 0.0 mmH2O

2 URV 2500.0 mmH2O

3 Unit mmH2O

4 LSL -10197.2 mmH2O

5 USL 10197.2 mmH2O

HELP

SAVE

HOME ENTER

EJX:YOKOGAWA

LRV

0.0 mmH2O

0.0

HELP

DEL

ESC

ENTER

2

Enter

500, and press ENTER (F4).

EJX:YOKOGAWA

Keypad input

1 LRV 500.0 mmH2O

2 URV 2500.0 mmH2O

3 Unit mmH2O

4 LSL -10197.2 mmH2O

5 USL 10197.2 mmH2O

DEL

HOME

3

To change the Upper Range

Value, select the

URV item.

To change the Lower Range

Value, select the

LRV item.

HELP

SEND

ENTER

(ENTER)

‘3 5 0 0’

(ENTER)

‘5 0 0’

(SEND)

EJX:YOKOGAWA

URV

2500.0 mmH2O

2500.0

HELP

ESC

4

Enter

3500, and press ENTER (F4).

DEL

ENTER

EJX:YOKOGAWA

Keypad input

1 LRV 500.0 mmH2O

2 URV 3500.0 mmH2O

3 Unit mmH2O

4 LSL -10197.2 mmH2O

5 USL 10197.2 mmH2O

HELP

HOME

5

Press

SEND (F2) to send the

changed data to the transmitter.

Check that disappears.

SEND

ENTER

SEND

Example: To change the range from

0 to 2500 mmH

2

O to

500 to 3500 mmH

2

O

1. Device setup
3. Basic setup
3. Re-range
1. Keypad input

Call up the

Keypad input display.

NOTE

The calibration range can be set as LRV > URV

under the following conditions, reversing the 4 to

20 mA output signal.

LSL ≤ LRV ≤ USL

LSL ≤ URV ≤ USL

|URV – LRV| ≥ Min. Span