Yokogawa EJX440A User Manual

Page 65

Advertising
background image

<5. Parameter Summary>

5-4

IM 01C25T01-01E

Function

Label

Item

Contents

Default value

Handling

Fast key

sequences

Process Alert Digital Output

Display of contact output

Off or On

Off

RA

1, 4, 3, 4, 7, 1

DO Select

Contact output select

Off, P Alarm, SP Alarm, P or

SP Alarm

Off

WA

1, 4, 3, 4, 7, 2

DO Signal type

Signal type select

On When Al Detect or Off

When Al Detect

On When Al

Detect

WA

1, 4, 3, 4, 7, 3

DO Test

Test output contact

Off, On, or Exit

MA

1, 4, 3, 4, 7, 4

Hi Alert Val

High side alert value of pressure

LSL–10% to USL+10% minus

5% hysteresis

W

1, 4, 3, 4, 2, 1

Lo Alert Val

Low side alert value of pressure

LSL–10% to USL+10% plus

5% hystereis

W

1, 4, 3, 4, 2, 2

Pres Alert mode

Alert mode for pressure

Off, Hi Al Detect, Lo Al Detect,

or Hi/Lo Al Detect

Off

W

1, 4, 3, 4, 1

SP Alert mode

Alert mode for static pressure

Off, Hi Al Detect, Lo Al Detect,

or Hi/Lo Al Detect

Off

WD

1, 4, 3, 4, 3

SP Hi Alert Val

High side alert value of static

pressure

SP LSL–10% to SP USL+10%

minus 5% hysteresis

WD

1, 4, 3, 4, 4, 1

SP Lo Alert Val

Low side alert value of static pressure SP LSL–10% to SP

USL+10% plus 5% hystereis

WD

1, 4, 3, 4, 4, 2

Temp Alert mode

Alert mode for temperature

Off, Hi Al Detect, Lo Al Detect,

or Hi/Lo Al Detect

Off

W

1, 4, 3, 4, 5

Temp Hi Alert Val

High side alert value of temperature

–50 to 130

120 degC

W

1, 4, 3, 4, 6, 1

Temp Lo Alert Val

Low side alert value of temperature

–50 to 130

–40 degC

W

1, 4, 3, 4, 6, 2

Process

variables

AO

Analog output current

3.6000 to 21.6000 mA

R

1, 1, 3

Engr Disp

User scaled value

Unit specified in Set Engr Unit

R

1, 1, 7

Engr Unit

User set engineering unit

Unit specified in Set Engr Unit

R

1, 1, 9

Pres

Measured pressure

Unit specified in Unit

R

1, 1, 1

Pres %

Measured pressure in %

–2.50 to 110.00%

R

1, 1, 2

Snsr temp

Capsule temperature

Unit specified in Temp Unit

R

1, 1, 6

SP

Measured static pressure

–32000 to 32000, unit

specified in SP Unit

RD

1, 1, 4

SP %

Measured static pressure in %

–10.0 to 110.00%

RD

1, 1, 5

Rerange

Apply values

Rerange for measured pressure

4 mA, 20 mA, or Exit

M

1, 3, 3, 2

LRV

Lower range value

LSL –10% to USL +10%

within measurement range

As specified

W

1, 3, 3, 1, 1

URV

Upper range value

LSL –10% to USL +10%

within measurement range

As specified

W

1, 3, 3, 1, 2

Self test

Self test

Self-diagnostics

See Chapter 4

M

1, 2, 1, 2

Sensor trim

Clear P snsr trim

Reset pressure trim to factory setting

M

1, 2, 3, 3, 5, 3

Clear SP snsr trim

Reset SP trim to factory setting

MD

1, 2, 3, 4, 4, 3

P LTD

Lower pressure trim deviation

R

1, 2, 3, 3, 5, 1

P LTP

Lower temperature trim point

R

1, 2, 3, 3, 3

P UTD

Upper pressure trim deviation

R

1, 2, 3, 3, 5, 2

P UTP

Upper temperature trim point

R

1, 2, 3, 3, 4

Pres trim

Pressure trim

M

1, 2, 3, 3, 2

Pres Zero trim

Zeroing

M

1, 2, 3, 3, 1

SP LTD

Lower SP trim deviation

RD

1, 2, 3, 4, 4, 1

SP LTP

Lower SP trim point

RD

1, 2, 3, 4, 2

SP UTD

Upper SP trim deviation

RD

1, 2, 3, 4, 4, 2

SP UTP

Upper SP trim point

RD

1, 2, 3, 4, 3

Static Pres trim

Static pressure trim

MD

1, 2, 3, 4, 1

Trim Date

Trim information

**/**/**

W

1, 2, 3, 5, 2

Trim Desc

Trim information

16 alphanumerics

W

1, 2, 3, 5, 4

Trim Loc

Trim information

8 alphanumerics

W

1, 2, 3, 5, 3

Trim Who

Trim information

8 alphanumerics

W

1, 2, 3, 5, 1

Signal

characterizer

Num of points

Number of coordinates

0 to 9

9

W

1, 4, 2, ↓, 2

Point setting

Coordinates editor

M

1, 4, 2, ↓, 3

S.C.

Signal characterizer permission

Disabled or Enabled

Disabled

W

1, 4, 2, ↓, 1

X End

End point of X

100.00%

R

1, 4, 2, ↓, 6

X Start

Start point of X

0.00%

R

1, 4, 2, ↓, 4

Y End

End point of Y

100.00%

R

1, 4, 2, ↓, 7

Y Start

Start point of Y

0.00%

R

1, 4, 2, ↓, 5

*1:

Handling:

R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, D=Applicable for differential pressure

transmitters. Do not change these parameters for pressure transmitters.

*2:

The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.