<3. Operation>

3-30

IM 01C25T01-01E

F0353.ai

1. Device setup
4. Detailed setup
2. Signal condition
T.Z. Cmp menu
2. Temp Zero

Example: Enter K value obtained from the equation (a).

A value haivng up to 3 decimal places may be

specified.

When

h=+3 m, Fill fluid code A, span=15 kPa,

K=−(+3)Ч0.00745ч15Ч100=−0.149

EJX:

Temp Zero

0.000 %/degC

-0.149

ESC

ENTER

1

2

(ENTER)

HELP

DEL

Enter

−0.149

and press

ENTER

(F4).

‘ −0.149 ’

EJX:

T.Z. Cmp menu

1 T.Z. Cmp mode On

2 Temp Zero

HELP

SEND

HOME ENTER

Press

SEND (F2) to send the data

to the transmitter, then check to

confirm that disappears.

(SEND)

SEND

Note 1: The function is performed using a built-in temperature

sensor in the transmitter body. The temperature

deviation between the transmitter body and capillaries

should be minimized to achieve optimal performance

of the function.

Note 2: When the span changes, reenter the newly obtained

value of K to

Temp Zero.

Table A. Constant value [B] of fill fluid

Fill fluid

code

A, C

B

D

E

C

on

st

an

t v

al

ue

[B

]

mmH

2

O

0.76

0.87

1.45

0.75

kgf/cm

2

0.000076 0.000087 0.000145 0.000075

kPa

0.00745

0.00853

0.01422

0.00736

mBar

0.07453

0.08532

0.14220

0.07355

atm

0.000074 0.000084 0.000140 0.000073

inH

2

O

0.02992

0.03425

0.05709

0.02953

psi

0.00108

0.00124

0.00206

0.00167

mmHg

0.05592

0.06401

0.10669

0.05518

Note 3: Select the unit of constant value of [B] from the actual

unit used for the transmitter in operation.