<3. Operation>

3-11

IM 01C25T01-01E

3.4.5 Damping Time Constant Setup

The damping time constant is set as specified in

the order when the instrument is shipped. Follow

the procedure below to change the damping

time constant. The damping time constant for the

amplifier assembly can be set here. The damping

time constant for the entire transmitter is the sum

of the values for the amplifier assembly and the

capsule assembly.
Any number from 0.00 to 100.00 can be set for the

damping time constant. Note that setting the quick

response parameter ON enables you to set the time

constant between 0.00 and 0.49 seconds.

1

Call up the

Quick resp display to set the value

to less than 0.5 seconds.

EJX:YOKOGAWA

Quick resp

Off

Off

On

HELP

DEL

ESC

ENTER

Select

On and press ENTER (F4).

(ENTER)

2

EJX:YOKOGAWA

Signal condition

7 Low cut mode

8 H/L Swap Normal

9 Bi-dir mode Off

Quick resp On

T.Z. Cmp menu

HELP

SEND

HOME ENTER

Press

SEND (F2) to send the data

to the transmitter.

1. Device setup
4. Detailed setup
2. Signal condition
Quick resp

Example: To change from

2.0 seconds to 0.5 seconds

1

F0313.ai

Call up the

Pres Damp display.

EJX:YOKOGAWA

Pres Damp

2.00 sec

0.5

HELP

DEL

ESC

ENTER

Enter

0.5 and press ENTER (F4).

(ENTER)

‘0 . 5’

2

EJX:YOKOGAWA

Basic Setup

3 Re-range

4 Device information

5 Xfer fncfn

6 Pres Damp 0.50 sec

7 Low cut 10.00 %

HELP

SEND

HOME ENTER

Press

SEND (F2) to send the data

to the transmitter.

1. Device setup
3. Basic setup
6. Pres Damp

3.4.6 Output Signal Low Cut Mode Setup

Low cut mode can be used to stabilize the output

signal near the zero point.
The low cut point can be set in a range from 0 to

20%, the direct ratio corresponding to the output

signal of 4 to 20 mA. (Hysteresis for the cut point:

±10% of the cut point)
Either

LINEAR or ZERO can be selected as the low

cut mode. Unless otherwise specified, the cut mode

is set to LINEAR at the factory.
Note that when the output modes of the output

signal and the display are selected as

Sq root

and

Linear accordingly, the low cut function is not

available for the display value.

(%)

50

(%)

50

0

50

(%)

50

(%)

Output

Output

For low cut in linear mode

Input

20

20

0

For low cut in zero mode

Input

F0314.ai

Example: To set the low cut range to 20% and the cut

mode to ZERO in the

Sq root output mode,

proceed as follows:

Figure 3.4.6 Low Cut Mode

F0315.ai

EJX:YOKOGAWA

Low cut

10.00 %

10.00

HELP

DEL

ESC

ENTER

Call up

Low cut, and set to 20%.

(ENTER)

(ENTER)

‘2 0’

EJX:YOKOGAWA

Low cut mode

Linear

Linear

Zero

HELP

SEND

ESC

ENTER

Select the

Low cut mode, and

set to

Zero.

EJX:YOKOGAWA

Basic Setup

4 Device information

5 Xfer fnctn Linear

6 Pres Damp 0.50 sec

7 Low cut 20.00 %

8 Low cut mode Zero

HELP

SEND

HOME

OK

Press

SEND (F2) to send the

date, then check to confirm that

disappears.

(SEND)

1. Device setup
3. Basic setup
7. Low Cut and 8. Low cut mode

SEND

1

2

3