<4. Diagnostics>

4-11

IM 01C25T01-01E

NOTE

The alarms of “Invalid Ref xx” and “ILBD over

range” do not link to the 4-20 mA analog signal

and Status output.

4.2.2.6 Condition Check

After the EJX differential pressure/pressure

transmitter was installed, it is necessary to confirm if

Pres is stable under the normal operating condition

or if fluctuation amplitude under the normal

operating condition is large enough to detect the

blockage.

Stability of Primary Value

1) Observe the value change of

Pres under the

normal operating condition for 10 minutes.

2) Confirm the value change is less than 10%.
If the value change is more than 10%, the error

influences pressure fluctuation value so that the

blockage detection becomes impossible. Consider

the plant operating conditions.

Fluctuation Value

NOTE

The blockage detection may not be carried

out correctly when pressure fluctuation

amplitude especially with the pressure and level

measurement, is small.

Confirm that each value of

fDP, fSPl, fSPh, and

BlkF is more than the value specified in the below

table.

Table 4.2.4 Requirements to apply ILBD

Condition

fDP

7×10

-10

or more

fSPI

1×10

-10

or more

fSPh

1×10

-10

or more

BlkF

-0.5 to 0.5

fDP is not enough.

No blockage can be detected if

fDP is not larger

than the specified value.

Only fDP is enough.

“A Blocking” or “B Blocking” can be detected

if

fSPl and fSPh are not larger than specified

values.

fDP and fSPl are enough.

“H Side Blocking” and “Large Fluct H” can not

be detected if

fSPh is not larger than specified

value.

fDP and fSPh are enough.

“L Side Blocking” and “Large Fluct L” can not

be detected if

fSPl is not larger than specified

value.

fDP, fSPl and fSPh are enough.

All alarm modes can be detected even if

BlkF is

not within the specified values.

4.2.2.7 Obtain Reference Values

The pressure fluctuation values are reduced

when the impulse line is plugged. Therefore, the

reference value is required to determine the degree

of reduction.

IMPORTANT

• If the impulse line is about to be plugged at

the time when a reference value is obtained,

blockages cannot be detected accurately.

The impulse lines on both the high-pressure

and low-pressure sides need to be cleaned

before a reference value is obtained.

• All air bubbles need to be adequately purged

before a reference value is obtained.

• Reference values must be obtained under

operating condition.

NOTE

Use Device description (DD) file for parameter

setting.