Yokogawa EJX440A User Manual

Page 45

Advertising
background image

<4. Diagnostics>

4-5

IM 01C25T01-01E

A/B Blocking Detection

“A Blocking” and “B Blocking” indicates the result

estimated from blockage degree based on the

difference of the high- and low-pressure-side

fluctuation values.

Ratio fDP, SQRT (fDP / Ref

fDP) is used to detect A/B blocking. Ref fDP is the

average value of the sum of squares of differential

pressure fluctuations under normal condition.
As the value of

Ratio fDP exceeds the value of

Lim fDPmax, EJX gives basically an alarm of “A

Blocking”. On the other hand, if this value is below

the value of

Lim fDPmin, EJX gives an alarm of “B

Blocking.
As a high- or low-pressure-side blockage

progresses,

fDP increases. Therefore, “A Blocking”

with a differential pressure transmitter indicates

that a single-side impulse line is plugged for a

differential pressure transmitter. As the both-side

blockages progress simultaneously,

fDP decreases.

Therefore, “B Blocking” with a differential pressure

transmitter indicates that both-side impulse lines

are plugged.

NOTE

A single-side impulse line blockage may

generate “B blocking” under the condition where

the fluctuation amplitude is much different

between high- and low-pressure sides.

With a transmitter to measure pressure or tank

level, “B blocking” only is detected.

H/L Blocking Detection

EJX differential pressure transmitter enables

to detect both-, a high-, or low-pressure-side

blockage. The blockage degree characterized

by a comparison of high-pressure side and low-

pressure-side fluctuation values,

BlkF, is used to

detect it. The value changes within a range of –1

to +1. As

BlkF approaches +1, the high-pressure-

side blockage progresses. On the other hand, if it

approaches –1, the low-pressure-side blockage

progresses.

1

0

1

0

F0406.ai

BlkF

Blockage detection for

high-pressure side

Threshold

Blockage Progress

BlkF

Blockage detection for

low-pressure side

Threshold

Blockage Progress

-1

-1

Figure 4.2.2 Relation between Blockage Progress

and BlkF

The each threshold value to detect the high- or low-

pressure-side blockage is set to

Lim BlkFmax or

Lim BlkFmin.

L Side Blocking Detection

BlkF is preferentially used to "L Side Blocking"

detection. If

BlkF cannot be used, Ratio fSPl,

SQRT (

fSPl / Ref fSPl) is used to "L Side Blocking"

detection.

Ref fSPl is the average value of the sum

of squares of low-pressure-side static pressure

fluctuations under normal condition.
As the value of

Ratio fSPl is below the value of Lim

fSPlmin, EJX gives an alarm of "L Side Blocking".
On the other hand, if this value exceeds the value of

Lim fSPlmax, EJX gives an alarm of “Large Fluct

L”.

H Side Blocking Detection

BlkF is preferentially used to "H Side Blocking"

detection. If

BlkF cannot be used, Ratio fSPh,

SQRT (

fSPh / Ref fSPh) is used to "H Side

Blocking" detection.

Ref fSPh is the average value

of the sum of squares of high-pressure-side static

pressure fluctuations under normal condition.
As the value of

Ratio fSPh is below the value

of

Lim fSPhmin, EJX gives an alarm of "H Side

Blocking".
On the other hand, if this value exceeds the value of

Lim fSPhmax, EJX gives an alarm of “Large Fluct

H”.

Large Fluctuation Detection

When a pump or compressor starts, the large

fluctuation is generated as process condition

changes rapidly. This phenomenon affects process

fluctuation measurement; so correct blockage

detection is not performed.

Advertising
This manual is related to the following products: