<4. Diagnostics>

4-6

IM 01C25T01-01E

If “Large Fluct L” or “Large Fluct H” is detected,

consider whether a blockage result is correct.
The threshold values to detect large fluctuation are

set to

Lim fSPlmax and Lim fSPhmax.

Since these values are enough to detect large

fluctuation, it is not almost necessary to change

them.

4.2.2.2 Combination of Reference Result

and Blockage Detection

An EJX differential pressure transmitter can detect

four modes of impulse line blockage: both-sides,

high-pressure side, low-pressure side, and/or

single-side when all the reference values are

properly measured. However, the detectable alarm

mode combination is limited when some of the

reference values are invalid. Available Blockage

Detection are shown in the below figure.

NOTE

Ref fDP must be larger than the specified

level shown in Table 4.2.4 (refer to 4.2.2.6).

No blockage can be detected when

Ref fDP

is not large enough.

• The plausibility of blockage detection needs

to be confirmed by blockage simulation test.

The simulation test can be performed by

the appropriate manifold operation (refer to

4.2.2.8).

[Transmitter for gauge/absolute pressure and level measurement]

[Differential pressure transmitter]

Ref fDP:

OK

Ref SPI:

OK

Ref SPh:

OK

Ref BlkF:

OK

Fluctuation Parameters

• Test for low-pressure side

• Test for high-pressure side

• Test for both-pressure sides

Simulation Test

• B Blocking detection

(by using

Ratio fDP)

• L Side Blocking detection

(by using

Ratio fSPI)

• H Side Blocking detection

(by using

Ratio fSPh)

• H/L Side Blocking detection

(by using

BlkF)

Ref fDP:

OK

Ref SPI:

OK

Ref SPh:

OK

Ref BlkF:

NG

• Test for low-pressure side

• Test for high-pressure side

• Test for both-pressure sides

• A/B Blocking detection

(by using

Ratio fDP)

• L Side Blocking detection

(by using

Ratio fSPl)

• H Side Blocking detection

(by using

Ratio fSPh)

Ref fDP:

OK

Ref SPI:

NG

Ref SPh:

OK

Ref BlkF:

NG

• Test for high-pressure side

• A Blocking detection

(by using

Ratio fDP)

• H Side Blocking detection

(by using

Ratio fSPh)

Ref fDP:

OK

Ref SPI:

NG

Ref SPh:

NG

Ref BlkF:

NG

• Test for both-pressure sides

• B Blocking detection

(by using

Ratio fDP)

Available Blockage Detection

Ref fDP:

OK

Fluctuation Parameters

Simulation Test

• Test for high-pressure side

• B Blocking detection

(by using

Ratio fDP)

Available Blockage Detection

F0407.ai