<3. Operation>

3-10

IM 01C25T01-01E

(2) Apply values — changing the ranges while

applying an actual Input

• This feature allows the lower and upper range

values to be setup automatically with the actual

input applied. If the upper and lower range

values are set, URV and LRV are changed at

the same time.

1

Press

OK (F4).

Call up the

Apply values display.

EJX:YOKOGAWA

WARN-Loop should be

removed from

automatic control

DEL

SET

ABORT

OK

EJX:YOKOGAWA

Set the:

1 4mA

2 20mA

3 Exit

HELP

SAVE ABORT ENTER

2

To set the lower range value, select

4mA and press ENTER (F4).

EJX:YOKOGAWA

Apply new 4ma input

HELP

DEL

ABORT

OK

3

Apply the pressure of 500mmH

2

O.

After obtaining a stable pressure,

press

OK (F4).

(ENTER)

(OK)

(OK)

1. Device setup
3. Basic setup
3. Re-range
2. Apply values

Example: To change the range from

0 to 2500 mmH

2

O to

500 to 3000 mmH

2

O

F0311.ai

EJX:YOKOGAWA

Current applied

process value: 500.01

mmH2O

1 Set as 4mA value

2 Read new value

3 Leave as found

DEL

ABORT

4

The LRV to be changed is 500.01

mmH

2

O.

• Selecting item 1 sets LRV to

500.01 mmH

2

O.

• Selecting item 2 reads LRV again.

To set LRV = 500.01, select item 1

and press

ENTER (F4).

HELP

SEND

ENTER

(ENTER)

EJX:YOKOGAWA

Set the

1 4mA

2 20mA

3 Exit

HELP

ABORT

5

Select

Exit and press ENTER (F4).

Check the value after completing the

range change with

URV and LRV.

* The span is maintained the same

as when changing LRV with

Apply values. In this case, if

LRV is changed from 0 to 500,

URV is changed automatically to

3000.

DEL

ENTER

×2

(ENTER)

• The measurement span is determined by the

upper and lower range values. Changing the

lower range value causes the upper range

value to change automatically, keeping the

span constant. If a change in the lower range

value causes the upper range value to exceed

the measuring limit of the transmitter, an error

message appears and the transmitter holds the

output signal right before the error occurred.

Enter the correct values within the range of the

sensor limits.

• Note that changing the upper range value does

not cause the lower range value to change.

Thus, changing the upper range value also

changes the span.

3.4.4 Output Mode

The mode setting for the output signal and the

integral indicator can be performed independently.
The output mode for the output signal is set as

specified in the order when the instrument is

shipped. Follow the procedure below to change the

mode.

1

F0312.ai

Call up the

Xfer fnctn display.

EJX:YOKOGAWA

Xfer function

Linear

Linear

Sq root

DEL

SET

ESC

ENTER

[1] Select

Sq root, and press

ENTER (F4).

[2] Press

SEND (F2) to send the

data to the transmitter, then

check to confirm that

disappears.

(ENTER)

1. Device setup
3. Basic setup
5. Xfer fnctn

(SEND)

SEND

Example: To change the mode from

Linear to Sq root.