<Appendix 2. ILBD Check List>

A-4

IM 01C25T01-01E

Appendix 2. ILBD Check List

Fill out the below checklist according to the operation flow of the ILBD in order to keep the important

information for the blockage detection.

Checklist (1/5)

No.

Items

Parameters

Result

Example

1

4-20 mA Analog Signal Setting

• Select the output mode when an alarm is

generaed.

Diag Out Option

Off: 

Burnout: 

Fall back: 

Diag Fixed Out Val

mA

21.6 mA

2

Status Output (option code AL)

DO Select

Pres: 

SP: 

Temp: 

Diag: 

All: 

3

Stability of Pres

(differential pressure/pressure)

under normal condition

• Check that the status of

Pres is “GOOD”.

• Check the maximum and minimum values of

Pres.

Status

Good

Pres

Max.:
Min.:

Max.: 12.3 kPa
Min.: 12.1 kPa

4

fDP under normal condition

• Check that the value of

fDP is more than

7x10

-10

.

fDP

5

Start to obtain Reference values

• Set "Reference" to

Diag Mode.

Diag Mode

6

End of Reference Value Sampling

• Check that

Diag Mode is “Calculation” after

the time set to "Diag Period" passed.

Diag Mode

7

Alarm setting

• Record the status of Checkbox in

Diag

Option.

Diag Option

A Blocking

Large Fluct L

Large Fluct H

L Side Blocking

H Side Blocking

B Blocking

Invalid Ref BlkF

Invalid Ref SPH

Invalid Ref SPL

Invalid Ref DP

ILBD over range