2 integral indicator display mode, 3 integral indicator scale setup, Integral indicator display mode -13 – Yokogawa EJX440A User Manual

Page 23: Integral indicator scale setup -13, And % of static pressure range, See (a.) through (d.) for the setting procedures

Advertising
background image

<3. Operation>

3-13

IM 01C25T01-01E

3.5.2 Integral Indicator Display Mode

The mode setting for the output signal and the

integral indicator can be performed independently.
The output mode for the integral indicator is set

as specified in the order when the instrument is

shipped. Follow the procedure below to change the

mode.

Example: Change from

Linear to Sq root.

F0319.ai

(ENTER)

EJX:YOKOGAWA

Disp Pres % fnctn

Linear

Linear

Sq root

HELP

SEND

ESC

ENTER

1. Device setup
4. Detailed setup
4. Display condition
2. P disp condition
1. Disp Pres % fnctn

Press

SEND (F2) to send the data

to the transmitter, then check to

confirm that disappears.

(SEND)

SEND

Call up the

Disp Pres % fnctn

Display. Select

Sq root, and

press

ENTER (F4).

EJX:YOKOGAWA

P disp condition

1 Disp Pres % fnctn

2 Disp Pres % Reso

3 Pres disp point 2

HELP

SEND

HOME

1

2

If the instrument is equipped with an integral

indicator and the transfer function is sq root, “

” is

displayed on the integral indicator.

3.5.3 Integral Indicator Scale Setup

The following five displays are available for integral

indicators: input pressure, % of range, user set

scale, input static pressure*

1

, and % of static

pressure range*

1

. A cycle of up to four displays can

be shown by assigning variables to the parameters

at

Disp select.

F0320.ai

Available displays

Input pressure

(PRES)

% of range

(PRES %)

User set scale

(ENGR. PRES)

Input static pressure

(SP)*

1

% of static pressure range

(SP %)*

1

Indicates values of input pressure

with the indication limits –99999 to

99999.

Indicates input pressure in –2.5 to

110% range depending on the

set range (

LRV and URV).

Indicates values depending on the

engineering range (

Engr LRV and

Engr URV) with the unit (Engr Unit).

Indicates input static pressure with

the indication limits –99999 to 99999.

Reference pressure is factory-set in

absolute.

Indicates input static pressure in

–10 to 110% range depending on

the set range (

SP LRV and SP

URV).

PRES

456 kPa

Description

and related parameters

PRES % 45.6 %

SP

4.000 MPa

SP %

52.6 %

Engr LRV 0.0

Engr URV 45.0

Engr exp ×100

Engr Unit m3/min

Engr point 1

*1: Available for differential pressure transmitter.

See (a.) through (d.) for the setting procedures.