3.5.8 Trim Analog Output

Fine current output adjustment is carried out with

D/A trim or Scaled D/A trim.

D/A Trim

D/A trim is to be carried out if the calibration

digital ammeter does not exactly read 4.000 mA

and 20.000 mA with an output signal of 0% and

100%.

Scaled D/A Trim

Scaled D/A trim is to be carried out if the output

is adjusted using a voltmeter or a meter whose

scale is 0 to 100%.

1

F0333-1.ai

Select the

D/A trim item.

EJX:YOKOGAWA

Analog output trim

1 D/A trim

2 Scaled D/A trim

3 Clear D/A trim

HELP

SAVE

HOME

OK

EJX:YOKOGAWA

WARN-Loop should be

removed from

automatic control

DEL

SET

ABORT

OK

2

Press

OK (F4).

EJX:YOKOGAWA

Connect reference

meter

HELP

DEL

ABORT

OK

3

Connect the ammeter (±1µA is

measurable), and press

OK (F4).

EJX:YOKOGAWA

Setting fld dev

output to 4mA

HELP

ABORT

4

Press

OK (F4), and the

transmitter outputs a 0% output

signal.

DEL

OK

(OK)

(OK)

(OK)

EJX:YOKOGAWA

Enter meter value

4.000

4.115

HELP

ESC

5

Enter the read value

4.115 of the

ammeter, and press

ENTER (F4).

(The output of the transmitter

changes.)

DEL

ENTER

(ENTER)

‘4 . 1 1 5’

Example 1: For an adjustment using an ammeter (±1µA is

measurable)

1. Device setup
2 Diag/Service
3. Calibration
2. Analog output trim
1. D/A trim

Ammeter reading: 4.115

6

F0333-2.ai

If the reading on the ammeter is

4.000 mA, select

YES and press

ENTER (F4).

If the reading is not 4.000 mA,

select item 2.

NO. Repeat steps

and until the ammeter

reads 4.000 mA.

EJX:YOKOGAWA

Fld dev output 4.000

mA equal to reference

meter?

1 Yes

2 No

HELP

SET

ABORT ENTER

EJX:YOKOGAWA

Setting fld dev

output to 20mA

DEL

SET

ABORT

OK

7

4

4

5

5

Press

OK (F4), and the

transmitter outputs a 100% output

signal.

EJX:YOKOGAWA

Enter meter value

20.000

19.050

HELP

DEL

ABORT ENTER

8

Carry out the same procedures as

those described under and .

EJX:YOKOGAWA

Fld dev output 20.000

mA equal to reference

meter?

1 Yes

2 No

HELP

ABORT

9

Returning fld dev to original

output appears.

DEL

ENTER

(OK)

(ENTER)

(ENTER)

‘1 9.0 5 0‘

EJX:YOKOGAWA

NOTE-Loop may be

returned to automatic

control

HELP

ESC

10

Press

OK (F4).

DEL

OK

(OK)

(ENTER)

Ammeter reading: 19.050

Ammeter reading: 20.000

Ammeter reading: 4.000