9 burst mode, 10 multidrop mode, Burst mode -22 – Yokogawa EJX440A User Manual

Page 32: Multidrop mode -22

Advertising
background image

<3. Operation>

3-22

IM 01C25T01-01E

3.5.9 Burst Mode

When the burst mode is set on, the transmitter

continuously sends stored data. Either the pressure

value, % range/current value, or current/process

variables can be selected and sent. The data is

sent approximately three times per second as a

digital signal when the transmitter is set in burst

mode. When data is being sent in burst mode,

other operations can be performed with the HART

communicator.

Setting of Burst Mode

F0335.ai

Call up the

Burst option, and set

the data to be sent.

• PV: Primary variable (Pressure

value)

• % range/current: Output in %

and mA

• Process vars/crnt: Output in

mA and process variables

(pressure value, static

pressure value, and sensor

temp value)

EJX:

Burst option

PV

PV

% range/current

Process vars/crnt

HELP

DEL

ESC

ENTER

EJX:

Burst mode

Off

On

Off

DEL

DEL

ESC

ENTER

Call up the

Burst mode and set

to

On.

HELP

(ENTER)

(ENTER)

1. Device setup
4. Detailed setup
3. Output condition
3. HART output
3. Burst mode
and 4. Burst option

EJX:

HART output

1 Poll addr 0

2 Num req preams 5

3 Burst mode On

4 Burst opiton PV

HELP

SEND

HOME ENTER

Press

SEND (F2) to send the

data to the transmitter, then

check to confirm that

disappears.

(SEND)

SEND

2

3

1

To release Burst Mode, call up the

Burst mode

display and set it to

Off.

3.5.10 Multidrop Mode

“Multidropping” transmitters refers to the connection

of several transmitters to a single communications

transmission line. Up to 15 transmitters can be

connected when set in the multidrop mode. To

activate multidrop communication, the transmitter

address must be changed to a number from 1 to

15. This change deactivates the 4 to 20 mA analog

output, sending it to 4 mA. The alarm current is also

disabled.

Setting of Multidrop Mode

F0336.ai

Call up the

Poll addr and set the

polling address. (a number from 1

to 15)

And press

SEND (F2) to send the

data.

EJX:

Poll addr

0

1

HELP

DEL

ESC

ENTER

HART Communicator

Polling

Ask Before Polling

Ask Before Polling

Always Poll

Digital Poll

Poll Using Tag

HELP

DEL

ESC

ENTER

Confirm that

Always Poll, Ask

Before Polling, or Digital Poll is

specified, and press

ENTER (F4).

(ENTER)

1. Device setup
4. Detailed Setup
3. Output condition
3. HART Output
1. Poll addr

2. Online
4. Utility
1. Configure Communication
1. Polling

Then make sure the communicator setting is as follows.

Advertising