<3. Operation>

3-5

IM 01C25T01-01E

Item

HART

communicator

Description

Page

Monitoring

Pres and Pres %

Pressure variable and % output variable

AO

4 to 20 mA output variable

Snsr temp

Sensor temperature

SP and SP %

Static pressure variable and % static pressure variable

Engr Disp/exp/Unit

Displays the output of user setting engineering information

Maintenance Test output

Loop test

Used for loop checks. Output can be set freely from –2.5% to

110% in 1% steps

P.3-16

Diagnostics

Self test and Status

Check using the self-test and status command. If an error is

detected, the corresponding message is displayed

P.4-1

Output when CPU

error has occurred

AO Alm typ

Display the status of 4 to 20 mA DC output when a failure occurs

P.3-24

External volume

switch

Ext SW

Display/set the external volume protect/permit for LRV (URV)

setting

P.3-23

Software write

protect

Write protect

Displays the permit/protect status of setting changes depending

on communications

P.3-25

Enable wrt 10min

Write protect status is released for 10 minutes when the

password is entered

P.3-25

New password

Sets a new password

P.3-25

Adjustment

Zeroing

Zero trim

Sets the current input value to 0 kPa

P.3-17

Sensor trim

Pres and SP sensor

trim

Adjust the measured differential pressure and static pressure

variables

P.3-17

Analog output trim

D/A trim, Scaled D/A

trim

Adjust the output value at the points of 4 mA and 20 mA

P.3-20

Signal characterizer

S.C. menu

Used for compensate the output for the non-linear application

P.3-26

Capillary fill

fluid density

compensation

T.Z. Cmp mode

Compensates the zero shift by the ambient temperature effect

on the capillary tubes

P.3-29