5 unit for displayed static pressure, 6 test output, Unit for displayed static pressure -16 – Yokogawa EJX440A User Manual

Page 26: Test output -16, Operation

Advertising
background image

<3. Operation>

3-16

IM 01C25T01-01E

3.5.5 Unit for Displayed Static Pressure

Follow the procedure to change the static pressure

unit.
Changing this parameter also changes the unit for

the static pressure display.

F0326.ai

(ENTER)

EJX:YOKOGAWA

SP Unit

mmH2O

kg/cm2

Pa

kPa

torr

HELP

SEND

ESC

ENTER

Select

kPa and Press ENTER

(F4).

1. Device setup
4. Detailed setup
1. Sensors
2. SP sensor
3. SP Unit

Example: Change the static pressure unit from

mmH

2

O to

kPa.

EJX:YOKOGAWA

SP sensor

1 SP 0 mmH2O

2 SP % 0.0 %

3 SP Unit kPa

4 A/G Select

5 SP H/L Select High

HELP

SEND

HOME ENTER

2

1

Press

SEND (F2) to send the data

to the transmitter, then check to

confirm that disappears.

(SEND)

SEND

3.5.6 Test Output

This feature can be used to output a fixed current

for loop checks. The available range for test output

depends on the settings for the

AO lower limit and

AO upper limit parameters, whose limit is from 3.6

mA (-2.5%) to 21.6 mA (110%) .

1

F0327.ai

Set the control loop in manual

mode, and press

OK (F4).

EJX:YOKOGAWA

WARN-loop should be

removed from

automatic control

DEL

SET

ABORT

OK

EJX:YOKOGAWA

Choose analog output

level

1 4mA

2 20mA

3 Other

4 End

DEL

SET

ABORT ENTER

2

Select

Other, and press ENTER

(F4).

Supplementary explanation.

1. 4 mA:

Outputs a 4 mA current signal

2. 20 mA:

Outputs a 20 mA current signal

3. Other:

Sets a desired output using the

alphanumeric keys

4. End: Exits

EJX:YOKOGAWA

Output
12

HELP

DEL

ABORT ENTER

3

Enter

12, and press ENTER (F4).

A fixed current of 12 mA is output.

EJX:YOKOGAWA

Fld dev output is

fixed at 12.000 mA

DEL

ABORT

4

Press

OK (F4).

HELP

SEND

OK

×2

(ENTER)

×3

(ENTER)

(ENTER)

(OK)

(OK)

‘1 2’

(OK)

EJX:YOKOGAWA

Choose analog output

level

1 4mA

2 20mA

3 Other

4 End

DEL

ABORT

5

To finish the loop test, select

End,

and press

ENTER (F4).

HELP

SEND

ENTER

EJX:YOKOGAWA

NOTE-loop may be

returned to automatic

control

DEL

ESC

6

Press

OK (F4).

HELP

SEND

OK

Example: To output 12 mA (50%)

1. Device setup
2. Diag/Service
2. Loop test