<4. Diagnostics>

4-7

IM 01C25T01-01E

4.2.2.3 Operation Parameters

Diag Mode

Diag Mode gives the directive for the ILBD

operation. There are following three modes.

Diag Mode

Index

Mode

Function

0

Stop

The blockage detection operation

is stopped.

1

Calculation

The blockage detection operation

is performed.

Alarms are generated along with

the result.

2

Reference

Reference values for the

blockage detection are obtained

and updated to the latest. After

sampling reference values, this

mode changes to "Calculation".

When the blockage detection operation is

performed, set “Calculation” to

Diag Mode. “Stop”

must be set when you change a threshold value or

set an alarm. “Reference” is set in order to obtain

the reference fluctuation values under the normal

configuration.

Diag Period

The values such as

Ratio fDP and BlkF are

averaged based on several hundreds of pressure

fluctuation values in constant time.

Diag Period

defines the sampling time is. The default value at

the shipment is set to 180 seconds.
For the information on how to change the sampling

period, refer to 4.2.2.10.

Diag Supp Count

When the value as

Ratio fDP or BlkF exceeds

the threshold value for several times in a row,

it is estimated that the impulse line is plugged.

Diag Supp Count defines the number of times to

estimate blockage detection.
If

Diag Supp Count is set to three times, an

alarm is not generated at part ‘A’ in Figure 4.2.3.

Because the first and second values only exceeded

consecutively the threshold.
When the value exceeds consecutively the

threshold value three times, an alarm is generated

(see part ‘B’ in Figure 4.2.3).

B

A

B

A

F0408.ai

Diag Supp Count (Number of times: 3)

Diag Supp Count (Number of times: 3)

Diag Period

Diag Period

Upper Threshold

(Ex.

Lim fDPmax)

Upper Threshold

(Ex.

Lim fDPmin)

An alarm is generated.

An alarm is generated.

Time

Time

Figure 4.2.3 Relationship of Diag Supp Count and

Alarm

The number of detection to give an alarm is set for

each blockage detection function. The default value

at the shipment is set to three times.
If fluctuating around the threshold value, an alarm

may be often generated. In this case, change the

threshold value (Limit parameter) or the sampling

time (

Diag Period) to enhance the accuracy of the

blockage detection. Refer to 4.2.2.10.