Yokogawa EJX440A User Manual

Page 60

Advertising
background image

<4. Diagnostics>

4-20

IM 01C25T01-01E

Integral

indicator

HART communicator

display

Cause

Output operation

during error

Countermeasure

Status

group

AL. 55

SP. ADJ

SP SPAN trim err

Continues to operate

and output.

Adjust settings and

change them as

needed.

7

SP ZERO trim err

AL. 60

SC. CFG

SC config error

Specified values or

settings do not meet the

conditions.

Continues to operate

and output without

signal characterizing.

Check settings and

change them as

needed.

AL. 79

OV. DISP

Displayed value

exceeds limit.

Continues to operate

and output.

AL.87

FLG. HI

FT high alarm

Flange temperature

exceeds a preset upper

limit.

It depends on the Diag

Out Option setting.

Off: Continue to

operate and

output.

Burnout:Outputs AO

upper limit or AO

lower limit.

Fall back:Outputs

Diag Out Fixed

Val.

Check the heater

failure.

Check the capsule

temp. and Amplifier

temp.

Adjust Flg Temp Coef.

8

AL.87

FLG. LO

FT low alarm

Flange temperature is

below a preset lower

limit.

AL.88

INVR.DP

Invalid Ref DP

Differential pressure/

pressure fluctuation

does not reach the

reference fluctuation

level required to

blockage detection

so that no blockage

detection is carried out.

Continue to operate

and output.

Check process

condition.

AL.88

INVR.SL

Invalid Ref SPL

Low-side-pressure

fluctuation fluctuation

does not reach the

reference fluctuation

level required to

blockage detection.

AL.88

INVR.SH

Invalid Ref SPH

High-side-pressure

fluctuation fluctuation

does not reach the

reference fluctuation

level required to

blockage detection.

AL.88

INVR.F

Invalid Ref F

BlkF can not be used for

blockage detection for

some reasons.

AL.89

ILBD.OV

ILBD over range

Appointed the diagnosis

range outside.

Check process

condition.

AL.89

B BLK

B Blocking

B Blocking (both- side

blockage) is detected.

It depends on the Diag

Out Option setting.

Off: Continue to

operate and

output.

Burnout: Outputs AO

upper limit or AO

lower limit.

Fall back: Outputs

Diag Out Fixed

Val.

Check process

condition.

9

AL.89

H BLK

H Side Blocking

High-pressure-side

blockage is detected.

AL.89

L BLK

L Side Blocking

Low-pressure-side

blockage is detected.

AL.89

H LRG

Large Fluct H

Pressure fluctuation

amplitude of high-

pressure side is large.

AL.89

L LRG

Large Fluct L

Pressure fluctuation

amplitude of low-

pressure side is large.

AL.89

A BLK

A Blocking

A Blocking (single-side

blockage) is detected.

Advertising