background image

<3. Operation>

3-8

IM 01C25T01-01E

3.4 Basic Setup

3.4.1 Tag and Device Information

To change the Tag No., see section 3.1.4 Entering,

Setting, and Sending Data.
Up to 8 characters can be set with

Tag. The

maximum number of characters to be set for other

items is as shown below.

Item

Number of characters

Tag

Descriptor

Message

Date

8

16

32

2/2/2

(1) Tag

1. Device setup
3. Basic setup
1. Tag

EJX:YOKOGAWA

Tag

YOKOGAWA

YOKOGAWA

HELP

DEL

ESC

ENTER

F0308-1.ai

(2) Descriptor

1. Device setup
3. Basic setup
4. Device information
2. Descriptor

EJX:YOKOGAWA

Descriptor

HELP

DEL

ESC

ENTER

F0308-2.ai

(3) Message

1. Device setup
3. Basic setup
4. Device information
3. Message

EJX:YOKOGAWA

Message

HELP

DEL

ESC

ENTER

F0308-3.ai

(4) Date

1. Device setup
3. Basic setup
4. Device information
4. Date

EJX:YOKOGAWA

Date

**/**/**

**/**/**

HELP

ESC

ENTER

F0308-4.ai

3.4.2 Unit

The unit parameter is set at the factory before

shipment if specified at the time of order. Follow the

procedure below to change the unit parameter.

F0309.ai

EJX:YOKOGAWA

Unit

mmH2O

MPa

inH2O

mmH2O

ftH2O

DEL

SAVE

ESC

ENTER

1

Select the desired unit and press

ENTER (F4).

HELP

(ENTER)

Example: To change the unit from

mmH

2

O to inH

2

O

EJX:YOKOGAWA

Basic setup

1 Tag YOKOGAWA

2 Unit mmH2O

3 Re-range

4 Device infomation

5 Xfer fnctn Linear

DEL

2

Press

SEND (F2) to send the new

unit to the transmitter memory.

HELP

SEND

HOME

DEL

HELP

SAVE

HOME

ENTER

(SEND)

EJX:YOKOGAWA

Basic setup

1 Tag YOKOGAWA

2 Unit mmH2O

3 Re-range

4 Device infomation

5 Xfer fnctn Linear

3

Check that becomes .

ENTER

SEND

SAVE

1. Device setup
3. Basic setup
2. Unit

Note that the Yokogawa default setting for the

standard temperature is 4°C (39.2°F). For the units

of mmH

2

O, inH

2

O, and ftH

2

O, the pressure varies

according to the standard temperature definition.

Select the appropriate unit with @68degF when a

standard temperature of 20°C (68°F) is required.
Available pressure units are shown below.

inH

2

O@68degF

inHg

ftH

2

O@68degF

mmH

2

O@68degF

mmHg

psi

bar

mbar

g/cm

2

kg/cm

2

Pa

kPa

torr

atm

MPa

inH

2

O

mmH

2

O

ftH

2

O

hPa