4.2.3 Heat Trace Monitoring

The EJX with Heat trace monitoring function

calculates the flange temperature by using the two

temperature sensors built in the EJX.
An analog alert is generated if the temperature

reached to the preset level.
The flange temperature is based on the following

parameters and calculation formula.

[Parameters]

Parameter name

Explanation

Snsr temp (CT)

Measured capsule temperature

value

Amp temp (AT)

Measured amplifier temperature

value

Flg temp (FT)

Flange temperature value

(Calculated value)

Flg temp Coef (Cf)

Coefficient to calculate flange

temperature

Flg temp Hi Alert Val Threshold to generate FT high

alarm

Flg temp Lo Alert Val Threshold to generate FT low

alarm

[Calculation formula]

Flg temp (FT) = CT + Cf

f

X (CT-AT)

If the flange temperature exceeds the value preset

to

Flg temp Hi Alert Val or Flg temp Lo Alert Val,

an alert is generated.

NOTE

• The flange temperature is calculated by

the calculation formula assumed that the

capsule part of EJX is heated up or kept

warm by an electrical heater or steam. In

the case of an atmosphere temperature

or less, the difference of temperature of

approximately 3 to 4 °C, may occur because

the amplifier temperature becomes higher

than the capsule temperature.

• Use Device description (DD) file for

parameter setting.

4.2.3.1 Flg Temp Coef Setting

The value calculated according to the following

procedure is set to

Flg temp Coef.

• To enhance the calculation accuracy of the

flange temperature, measure the actual flange

temperature by using the temperature sensor

etc.

• Calculate the ratio of the capsule temperature

to the capsule temperature minus the amplifier

temperature from the two temperature values

measured by EJX.

• Derive the

Flg temp Coef from the measured

flange temperature and the ratio of the capsule

temperature to the amplifier temperature in

accordance with the following calculation

formula.

Flg temp Coef (Cf) =

(Actual measured value of Flange temperature) - CT

CT - AT

Amplifier

Temperature

Capsule

Temperature

Amp temp

Snsr temp

Flg temp Coef

Flg temp

Execution HTM

CT+(CT-AT) x Cr

Calculation of

Flg temp

Snsr temp

Flg temp

Diag Error

Display on LCD

Response Code

(Device Status)

Status group 8

Contact Output

Digital Output

Output 4-20mA

AO

Amp temp

Sensor signals

Sensor

Process Value

calculation

Alarm Masking

Result of HTM detection

HTM alarm

Result of HTM detection

DO Config

HTM alarm

HTM alarm

Diag Output

Option

F0414.ai

Figure 4.2.8 Functional Block Diagram of Heat Trace Monitoring