<3. Operation>

3-12

IM 01C25T01-01E

The low cut point has hysteresis so that the output

around the point is behaved as below figure.
<Example>

Output mode: Linear

Low cut mode: Zero

Low cut: 20.00%

F0354.ai

Setting range: 0 to 20%

2% 2%

4mA

Output

Low cut point

Input

Hysteresis

fixed at 10%

of the cut point

7.2mA

(20%)

3.4.7 Impulse Line Connection Orientation

Setup

This function reverses the impulse line orientation.

Follow the procedure below to make this change.

F0316.ai

(ENTER)

EJX:YOKOGAWA

H/L Swap

Normal

Normal

Reverse

HELP

SEND

ESC

ENTER

Press

SEND (F2) to send the

data to the transmitter, then

check to confirm that

disappears.

(SEND)

1. Device setup
3. Basic setup
9. H/L Swap

SEND

Call up the

H/L Swap Display

Select

Reverse, and press

ENTER (F4).

EJX:YOKOGAWA

Basic setup

5 Xfer fnctn Linear

6 Pres Damp 0.50 sec

7 Low cut 20.00 %

8 Low cut mode Zero

9 H/L Swap Reverse

HELP

SEND

HOME

Example: Assign the high pressure impulse line connection

to the L side of the transmitter.

1

2

3.5 Detailed Setup

3.5.1 Bi-directional Flow Measurement

(a) Bi-dir mode enables selection of 50% output at

an input of 0 mmH

2

O.

F0317.ai

(ENTER)

EJX:YOKOGAWA

Bi-dir mode

Off

off

on

HELP

SEND

ESC

ENTER

1. Device setup
4. Detailed setup
2. Signal condition
9. Bi-dir mode

Example: If measurement range is 0 to 3000mmH

2

O

(LRV = 0 mmH

2

O, URV = 3000 mmH

2

O)

Press

SEND (F2) to send the data

to the transmitter, then check to

confirm that disappears.

Note: The measurement range changes to −3000 to 0 to

3000 mmH

2

O, corresponding the output of 0% to

50% to 100%. Note that LRV and URV values are

not changed.

(SEND)

SEND

Call up the

Bi-dir mode display

Select

on, and press ENTER (F4).

EJX:YOKOGAWA

Signal condition

5 Pres Damp 0.50 sec

6 Low cut 20.00 %

7 Low cut mode Zero

8 H/L swap Reverse

9 Bi-dir mode On

HELP

SEND

HOME

1

2

(b) Combining

Bi-dir mode with Xfer fnctn

provides a square root output computed

independently for 0% to 50% output and for

50% to 100% output.

20 mA (100% display)

4 mA (−100% display)

Output mode “LINEAR”

LRV

HRV

F0318.ai

20 mA (100% display)

Low Cut

4 mA (−100% display)

Output mode “SQUARE ROOT”

LRV

HRV