15 process alarm, 16 status output (option code al), Process alarm -27 – Yokogawa EJX440A User Manual

Page 37: Status output (option code al) -27, Caution

Advertising
background image

<3. Operation>

3-27

IM 01C25T01-01E

3.5.15 Process Alarm

The function is used to display the alarm codes

when the input pressure exceeds the specified

value within the calibration range. The same is

available for the input static pressure and the

capsule temperature on the pressure sensor. Refer

to table 4.3.1 Alarm Message Summary for the

specific alarm code to be generated.

F0347.ai

(ENTER)

EJX:

Pres Alert mode

Off

Off

Hi. Al Detect

Lo. Al Detect

Hi/Lo. Al Detect

HELP

DEL

ESC

ENTER

Select

Hi. Al Detect, and press

ENTER (F4).

1. Device setup
4. Detailed setup
3. Output condition
4. Process Alerts
1. Pres Alert mode

Example: Set the alert mode from

OFF to Hi. Al Detect for

the input pressure.

EJX:

Process Alerts

1 Pres Alert mode

2 Config Pres Alerts

3 SP Alert Mode Off

4 Config SP Alerts

5 Temp Alert Mode

HELP

SEND

HOME ENTER

Press

SEND (F2) to send the data

to the transmitter, then check to

confirm that disappears.

(SEND)

SEND

1

2

F0348.ai

(ENTER)

EJX:

Hi Alert Val

100.000 kPa

75

HELP

DEL

ESC

ENTER

Enter 75, and press

ENTER (F4).

1. Device setup
4. Detailed setup
3. Output condition
4. Process Alerts
2. Config Pres Alerts
1. Hi Alert Val

Example: Set the higher alert value of 75 for alarm

generation.

EJX:

Config Pres Alerts

1 Hi Alert Val

2 Lo Alert Val

3 LSL -100.000 kPa

4 USL 100.000 kPa

HELP

SEND

HOME ENTER

Press

SEND (F2) to send the data

to the transmitter, then check to

confirm that disappears.

(SEND)

SEND

1

2

‘ 75 ’

NOTE

When option code /DG6 is specified,

Diag can

be also assigned to Status. The Hi Alert Val or

Lo Alert Val for

Diag is defined by the following

parameters.

[Impulse Line Blockage Detection]

Limit meters to detect the blockage and

Condition error for ILBD operation is defined.

Refer to 4.2.2.1.
[Heat Trace Monitoring]

Flg temp Hi Alert Val and Flg temp Lo Alert

Val parameters are used as the upper and

lower threshold for Status output. Refer to

4.2.3.2.

3.5.16 Status Output (option code AL)

This feature is used for a transistor output (open

collector) of an on/off signal according to the status

of high and low alarm limits, which are user-

configurable values as shown in 3.5.15 Process

Alarm. The status output can be assigned as

any combination of the high or low limits of the

input pressure, input static pressure, or capsule

temperature.

CAUTION

Whenever turning on the transmitter or detecting

the short interruption, check if contact output

correctly reflects the alarm status and test

the ON/OFF action of contact output by the

parameter "DO test" to confirm that the contact

output operates correctly.

NOTE

No status output signal has been defined for a

CPU failure or hardware error. Use a 4-20 mA

signal to indicate a transmitter’s failure.