<4. Diagnostics>

4-13

IM 01C25T01-01E

5) Check also the operation of the analog alert if

an analog alert is set.

6) Open the valve completely and check that

there are no alarms.

Simulation of Both-pressure Side

Blockage

1) Close the both-pressure-side valves.

2) Confirm the value of

Pres is stable. If not,

open the valve a little.

3) Set “Calculation” to

Diag Mode so as to start

blockage detection operation.

4) Check that an alarm of “B Blocking” is

generated after the time that consists of

Diag

Period and Diag Supp Count passed.

5) Check also the operation of the analog alert if

an analog alert is set.

6) Open the valve completely and check that

there are no alarms.

4.2.2.9 Start ILBD Operation

NOTE

Use Device description (DD) file for parameter

setting.

If process condition and capability to detect a

blockage are confirmed, you can start the ILBD

operation according to the following procedure.

1) Check the value of sampling period (

Diag

Period).

2) Check the number of times that detect the

blockage consecutively in order to give an

alarm (

Diag Supp Count). The default value

at the shipment is set to 3 times.

3) Set “Calculation” to

Diag Mode.

If the reference value has not yet been

obtained, set “Reference” to

Diag Mode.

After obtained the reference values, the

ILBD starts automatically. At the same time,

Diag Mode changes automatically from

“Reference” to “Calculation”.

4.2.2.10 Tuning

NOTE

Use Device description (DD) file for parameter

setting.

When the pressure fluctuation amplitude in fluids is

not sufficiently large or an alarm is often generated

according to the process condition, tune up by

changing the threshold for the blockage detection

(Limit parameters) or the sampling period (

Diag

Period) to enhance the accuracy of the blockage

detection The ILBD operation must be stopped to

tune up. Set “Stop” to

Diag Mode.

Threshold Value

The figure below shows the image of tuning effect

with a monochrome bar.
(a) The tuning image of the threshold values for

(1)

Ratio fDP: Sqrt (fDP/Ref fDP),

(2)

Ratio fSPl: Sqrt (fSPl/Ref fSPl),

(3)

Ratio fSPh: Sqrt (fSPh/Ref fSPh)

F0413-1.ai

0

1

3

Threshold (lower side)

Threshold (upper side)

(1)

Lim fDPmin

(2)

Lim fSPlmin

(3)

Lim fSPhmin

(1)

Lim fDPmax

(2)

Lim fSPlmax

(3)

Lim fSPhmax

(b) The tuning image of the threshold values for

(4) Sqrt (

BlkF/Ref BlkF)

F0413-2.ai

0

-1

1

Threshold (lower side)

Threshold (upper side)

(4)

Lim BlkFmin

(4)

Lim BlkFmax

Figure 4.2.7 Tuning Image of Threshold Value

Move the threshold toward the white.

• It becomes increasingly likely to give a false

alarm due to the disturbance from environment

change.

• If flow/differential pressure is below

Lim

DPAvgmin or exceeds Lim DPAvgmax,

pressure fluctuation is likely too small or too

large to detect the blockage.

Move the threshold toward the black.

• It enables to be insusceptible to disturbance

such as environment change and to detect the

blockage easier.

• It becomes giving an alarm of the blockage after

the blockage has been progressed.