<4. Diagnostics>

4-10

IM 01C25T01-01E

NOTE

Use Device description (DD) file for parameter

setting.

Alarm Masking

Diag Option

The alarms linked to an analog alert and LCD

display are selected by

Diag Option.

The bit of

Diag Option is corresponding to that

of

Diag Error. The following alarms are set at

the factory setting, which is corresponding to

hexadecimal 0x08FC.

• A Blocking

• Large Fluct L

• Large Fluct H

• L Side Blocking

• H Side Blocking

• B Blocking

• Invalid Ref DP

To Link the alarm to an analog alert and LCD

display, follow the procedure below.
1) Set “Stop” to

Diag Mode.

2) Check each checkbox of the alarm, which is

selectable from bit 2 to 14.

Note: Set to “Calculation” after setting the parameter.

Alert Setting

Diag Out Option

When an alert regarding the impulse line blockage

or high/low flange temperature is generated, the

output value of 4-20 mA analog signal can be

changed.

Code

Mode

Function

0

Off

Keeping PV measurement. The alert

is not reflected to 4-20 mA analog

signal.

1

Burnout

The analog signal is shifted to the

value of

AO upper limit or AO lower

limit when an alert is generated.

The shifted direction follows Burnout

switch setting.

2

Fall back

The analog signal is hold to the

specific value,

Diag Fixed Out Val,

when an alert is generated.

Diag Fixed Out Val

This parameter is used when “Fall back” is selected

to

Diag Output Option.

When an alert is generated, the 4-20 mA analog

signal is held on the value specified by this

parameter.
The value can be entered within 3.6 to 21.6 mA.

Status Output for Advanced diagnostic

(option code AL)

The output of the abnormal results are applicable

for a transistor output (open collector) of an on/off

signal according to the status of high and low alarm

limits, which are values set to Limit parameters

as shown in 4.2.2.1,

Flg temp Hi Alert Val, or Flg

temp Lo Alert Val (Refer to 4.2.3.2).

DO Select

If the advanced diagnostic function is installed, the

following modes can be also assigned to the status

output in addition to Pres, SP, and Temp.

Code

Mode

Function

8

Diag Alarm

The status regarding advanced

diagnostic masked by

Diag Option

is output.

9

All

All status of Press, SP, Temp, and

advanced diagnostic are output.

Alarm Display on LCD

If the ILBD algorithm detects the abnormality, the

content of the detected result is displayed with

“AL.88” or “AL.89” on the LCD. “AL.88” indicates

that condition is not applicable for the abnormality

detection and “AL.89” indicates the abnormality is

detected.

F0412.ai

Figure 4.2.6 Display Example of H Side Blocking

The alarm display on LCD regarding the advanced

diagnostic is described in Table 4.3.1.