Yokogawa EJX440A User Manual

Page 24

Advertising
background image

<3. Operation>

3-14

IM 01C25T01-01E

a. Display Selection
At

Disp select, select the variable that the

parameter

Disp Out 1 will display on the integral

indicator.

Example: Change from

PRES % to PRES for the display.

F0321.ai

(ENTER)

EJX:YOKOGAWA

Disp Out 1

PRES %

PRES %

ENGR. PRES

SP

SP %

HELP

SEND

ESC

ENTER

1. Device setup
4. Detailed setup
4. Display condition
1. Disp select
1. Disp Out 1

Press

SEND (F2) to send the

data to the transmitter, then check

to confirm that disappears.

(SEND)

SEND

Call up the

Disp Out 1 display.

Select

PRES, and press ENTER

(F4).

EJX:YOKOGAWA

Disp select

1 Disp Out 1 PRES

2 Disp Out 2 Not Used

3 Disp Out 3 Not Used

4 Disp Out 4 Not Used

HELP

SEND

HOME

1

2

b. Cyclic Display
In addition to the display set at

Disp Out 1, displays

can be set at

Disp Out 2, Disp Out 3, and Disp

Out 4 for cyclic display in the order of the parameter

number.
c. Setting Static Pressure Scale
Static pressure can be displayed as a measured

input or as a percentage, independent from the

4-20 mA output signal for measured pressure or

differential pressure. The

SP setup parameters

under

SP sensor allow the setting of the range,

unit, and damping time constant for the static

pressure as well as the pressure management

range for PV.
Note that either the high or low pressure side of

the capsule can be selected to monitor the static

pressure by means of the

H/L Select parameter

under

SP setup.

d. User Setting of Engineering Unit and Scale
Enter disp range
parameters allow the engineering

unit and scale to be displayed. At

Set Engr Unit,

the following engineering units can be selected

from a list. Alternately, up to eight alphanumeric

characters, spaces or slashes (/) can be input on

the keypad at

Modify Engr Unit; only the first six

are displayed on the integral indicator.
Select the unit from the

Set Engr Unit list.

kPa

MPa

mbar

bar

psi

psia

mmH2O

mmHg

mmHgA

mmAq

mmWG

Torr

inH2O

inHg

inHgA

ftH2O

gf/cm2

kgf/cm2

kg/cm2G

kg/cm2A

atm

kg/h

t/h

m3/h

m3/min

l/h

l/min

kl/h

kl/min

Nl/h

Nl/min

Nm3/h

Nm3/min

ACFH

ACFM

SCFH

SCFM

GPH

GPM

m

mm

in

ft

kg/m3

g/cm3

Follow the procedure below to set your own unit.

Example: Set the engineering unit as

M/h.

F0322.ai

EJX:YOKOGAWA

Enter Engr Unit:
M/H

HELP

DEL

ABORT ENTER

1. Device setup
4. Detailed setup
4. Display condition
4. Engr disp range
7. Modify Engr Unit

Call up the

Modify Engr Unit.

Set

M/H, and press ENTER (F4).

1

(ENTER)

EJX:YOKOGAWA

Enter space on the

characters to be

lowercase:

M/H

M/

HELP

DEL

ABORT ENTER

Enter a space instead of a

character to display the character

in lowercase, and press

ENTER

(F4).

2

(ENTER)

Ч2