<4. Diagnostics>

4-18

IM 01C25T01-01E

4.2.3.2 Out of Temperature Measurement

Range

When the flange temperature is out of

measurement range, the alarm or alert is

generated. For the detail of alarm and alert setting,

refer to 4.2.2.5.
The measurement range is set to

Flg temp Hi Alert

Val and Flg temp Lo Alert Val, which values can

be specified within -50 to 130 deg C.

Flgtemp

Flg temp

F0415.ai

Time

Time

An alarm is generated.

An alarm is generated.

Flg temp Hi Alert

Flg temp Lo Alert

4.2.3.3 Parameter Lists for Heat Trace Monitoring

#

Peman retemara

Deulav tiuafe

Expanation

1 Diag Error

0x0000

The results detected by ILBD or Heat trace monitoring are into this

parameter. Also the condition abnormality in the diagnostic process is

stored as an error.

2 Diag Option

0x08FC

The masking in this parameter enable to display each error message and

the status to the output signal or LCD.

The error assigned to each bit is corresponding to that of Diag Error.

Writable only when Diag Mode is "Stop".

3 Diag Out Option

Off

The error status can be output by 4-20 mA analog signal.

There are following three output modes; Off, Burnout, or Fall back.

4 Diag Fixed Out Val

21.6mA

Parameter for "Fall back" function in the Diag Out option.

The output value in 4-20 mA analog signal is specified when an alarm is

generated.

The value must be entered within 3.6 to 21.6 mA.

5 Snsr temp

Measured capsule temperature value

6 Amp temp

Measured Amplifier temperature value

7 Flg temp

(Note)

Calculated flange temperature value

8 Flg temp Coef

0

Coefficient to calculate flange temperature (Cf: Rt

1

/Rt

2

)

Rt

1

: Thermal resistance between the flange and capsule.

Rt

2

: Thermal resistance between the cupsule and amplifier.

9 Flg temp Hi Alarm Val

120 deg C

Upper limit of

Flg temp

10 Flg temp Lo Alarm Val

-40 deg C

Lower limit of

Flg temp

11 DO Select

Off

See.3.5.16 Status Output (option code AL)

12 DO Signal type

ON WHEN

AL DETECT

See.3.5.16 Status Output (option code AL)

13 Digital Output

Off

See.3.5.16 Status Output (option code AL)

Note: The

Flg temp Coef is 0 at the shipment so that the Flg temp outputs the same value as that of Snsr temp.