<4. Diagnostics>

4-9

IM 01C25T01-01E

4.2.2.5 Alarm and Alert Setting

The abnormal results as the blockage detection and

high/low flange temperature (heat trace monitoring)

are given through an analog alert or the LCD

display of alarm status. Before performing the ILBD

operation, it is necessary to set the alarm and alert

according to the following procedure.

Storage of Abnormal results

(Diag Error)

Alarm Masking

(Diag Option)

Outside Diagnosis Range/

Invalid Ref xx

Masking

Alarm on

Analog Output

Alarm on

Status Output

Device Status

Field Device More Status Available

Additional Device Status

(Status group 8 and 9)

Alarm Display

on LCD

F0410.ai

Figure 4.2.5 Alarm and Alert Setting

Alarm Status

When the algorithm of ILBD and Heat trace

monitoring detect the abnormality, the result is

stored in

Diag Error. The alarm status based on the

detected abnormality is displayed to

Diag Error.

Diag Error

Bit

Alarm status

Category

0 Not used.
1 Not used.
2 A Blocking

ILBD

3 Large Fluct L
4 Large Fluct H
5 L Side Blocking
6 H Side Blocking
7 B Blocking
8 Invalid Ref F
9 Invalid Ref SPH

10 Invalid Ref SPL

11 Invalid Ref DP

12

ILBD over range
(Outside Diagnosis Range)

13 FT high alarm

Heat trace

monitoring

14 FT high alarm
15 Not used.

Note: FT indicates the flange temperature.

ILBD over range (Outside Diagnosis

Range)

1) Lim DPAvgmax

Lim DPAvgmax is the upper limit of the

diagnostic capability range. The limit value can

be changed when

Diag Mode is “Stop”.

DPAvg indicates the ratio of the average of

differential pressure to the EJX maximum span

regarded as 1. When

DPAvg exceeds this

limit, “ILBD over range” is generated so that the

blockage detection becomes impossible.

2) Lim DPAvgmin

Lim DPAvgmin is the lower limit of the

diagnostic capability range. The limit value can

be changed when

Diag Mode is “Stop”.

When

DPAvg is below this limit, “ILBD over

range” is generated so that the blockage

detection becomes impossible.

<Example>

When the level range that can be measured by the

transmitter with 100 kPa span is –80 to 80 kPa, the

limits are set as follows.

Lim DPAvgmax: 0.80

Lim DPAvgmax: –0.80

1.000

0.000

0.80

-0.80

-1.000

Detectable
range

DPAvg

ILBD over range

ILBD over range

F0411.ai

Invalid Ref F, SPH, SPL, or DP

This alarm indicates that the reference value under

normal condition is invalid. If

Ref F is invalid, the

blockage detection excluding

BlkF is carried out.

If blockage detection function based on

BlkF is

required, obtain the reference value again.
Also when

Ref DPAvg is below Lim DPAvgmin

or exceeds

Lim DPAvgmax, all reference value

becomes invalid so that “Invalid Ref fDP”, “Invalid

Ref fSPl”, “Invalid Ref fSPh”, and “Invalid F” are

generated.