<10. Other Functions>

10-13

IM 11M12A01-04E

Output-related Items in Group C

Code

Item

Tuning

Engineering unit

Default setting

C01 Analog output

0 Oxygen concentration

Oxygen

concentration

1 Amount of moisture content
2 Mixed ratio

C03 Output mode

0 Linear

Linear

1 Logarithm

C04 Output during warm-up

0 Held at 4 mA

Held at 4 mA.

1 Held at 20 mA
2 Set value remains held.

C05

Output during maintenance 0 Not held

Held output just

before maintenance

service.

1 Held output just before

maintenance service.

2 Set value remains held.

C06 Output during calibration

0 Not held

Held output just

before calibration.

1 Held output just before calibration.
2 Set value remains held.

C07 Output during error

occurrence

0 Not held

Held output at a

preset value.

1 Held output just before abnormal

state occurs.

2 Set value remains held.

C11 Min. oxygen concentration See Section 8.2.

% O

2

0% O

2

C12 Max. oxygen concentration See Section 8.2.

% O

2

25% O

2

C30 Output damping constant

0 to 255

Seconds

0 second

C31 Set value during warm-up

2.4 to 21.6

mA

4 mA

C32 Set value during

maintenance

2.4 to 21.6

mA

4 mA

C33 Set value during calibration 2.4 to 21.6

mA

4 mA

C34 Set value in abnormal state 2.4 to 21.6

mA

3.4 mA

Note: "C07" and "C34" is not displayed when option code "/C2" or "/C3" (NAMUR NE 43 compliant) is specified.

Alarm-related Items in Group D

Code

Item

Tuning

Engineering unit

Default setting

D01 Oxygen concentration,

high-high alarm setpoint

0 to 100

% O

2

100% O

2

D02 Oxygen concentration,

high alarm setpoint

0 to 100

% O

2

100% O

2

D03 Oxygen concentration,

low alarm setpoint

0 to 100

% O

2

0% O

2

D04 Oxygen concentration,

low-low alarm setpoint

0 to 100

% O

2

0% O

2

D30 Oxygen concentration

alarm hysteresis

0 to 9.9

% O

2

0.1% O

2

D33 Delayed alarm action

0 to 255

Seconds

3 seconds

D41 Oxygen concentration,

high-high alarm detection

0 Not detected

Not detected

1 Detection

D42 Oxygen concentration,

high alarm detection

0 Not detected

Not detected

1 Detection

D43 Oxygen concentration,

low alarm detection

0 Not detected

Not detected

1 Detection

D44 Oxygen concentration,

low-low alarm detection

0 Not detected

Not detected

1 Detection