<Appendix B List of Messages>

B-1

IM 11B06C01-01E

Appendix B List of Messages

This Appendix contains a list of error messages displayed during Engineering Terminal

operations and the countermeasures to be taken.

n

Ethernet LCD Emulator Window

Message

Meaning

Countermeasures

St

ar

t

EtherLCD cannot execute

more than 5 on a PC.

More than 5 EtherLCDs are

operated on a PC at a same time.

4 is Maximum number of

EtherLCD to be connected at a

same time.

C

on

ne

ct

io

n

Other EtherLCD connects

with the analyzer

(xxx.xxx.xxx.xxx).

The appointed IP address of the

analyzer is now connecting with

(xxx.xxx.xxx.xxx) of the EtherLCD.

An analyzer cannot communicate

with the multiple EtherLCD at a

same time. Execute the command

again after disconnecting the

current connection.

The communication has

failed, because the Analyer is

local mode.

The communication cannot be

started because the analyzer is

under local mode.

Change from local mode to

remote mode at the anlyzer, then

command again.

Cannot open communication

device.

The communication cannot be

started due to a communication

device problem.

Check the Ethernet card, setting

of TCP/IP and Operation status of

the analyzer.

Fo

rc

e

co

nn

ec

t Password is incorrect.

Force connection is not

possible.

The entered password is invalid at

the force connection.

Enter the correct password.

O

n-

Li

ne

Communication with Analyzer

xxx has been cut.

The communication has failed

between the PC and the analyzer.

Check the network between the

PC and the analyzer, then try to

connect again.

Other PC starts the force

connection.

xxx.xxx.xxx.xxx.

The communication has failed

due to the force connection by

EtherLCD of IP address xxx.xxx.

xxx.xxx.

After ending the communication

with IP address xxx.xxx.xxx.xxx,

make the connection again.

An

al

yz

er

s

el

ec

t

di

al

og

This IP address is incorrect.

Invalid IP address is entered.

Enter the correct IP address.

This IP address overlaps with

analyzer xxx.xxx.xxx. xxx.

The entered IP address is

duplicated the analyzer xxx.xxx.

xxx.xxx.

Set the different IP address.

The analyzer ID is out of

range.

Invalid Analyzer ID is entered.

Set the valid analyzer ID. The

range is 1 to 240.

5th Edition : Nov. 16, 2011-00