SECTION 6 - JLG CONTROL SYSTEM

6-80

– JLG Lift –

3121181

MAIN LIFT PVG VALVE COMMAND
IMPROPER

Main boom lift pvg valve received an invalid command from the con-
trol system.

TOWER LIFT PVG VALVE COMMAND
IMPROPER

Tower boom lift pvg valve received an invalid command from the
control system.

TOWER TELESCOPE PVG VALVE COM-
MAND IMPROPER

Tower boom telescope pvg valve received an invalid command from
the control system.

MAIN LIFT PVG VALVE TIMEOUT

Main boom lift pvg valve has not received a position command in
250mS.

TOWER TELESCOPE PVG VALVE TIME-
OUT

Tower boom lift pvg valve has not received a position command in
250mS.

TOWER TELESCOPE PVG VALVE TIME-
OUT

Tower boom telescope pvg has not received a position command in
250mS.

MAIN LIFT PVG VALVE SETUP FAULT

Main boom lift pvg valve setup data is incorrect. Requires a valve cal-
ibration.

TOWER LIFT PVG VALVE SETUP FAULT

Tower boom lift pvg valve setup data is incorrect. Requires a valve
calibration.

TOWER TELESCOPE PVG VALVE SETUP
FAULT

Tower boom telescope pvg valve setup data is incorrect. Requires a
valve calibration.

MAIN LIFT PVG VALVE SENT UNRECOG-
NIZED FAULT

Main boom lift pvg valve sent an unrecognized fault.

TOWER LIFT PVG VALVE SENT UNREC-
OGNIZED FAULT

Tower boom lift pvg valve sent an unrecognized fault.

TOWER TELESCOPE PVG VALVE SENT
UNRECOGNIZED FAULT

Tower boom telescope pvg valve sent an unrecognized fault.

MAIN LIFT PVG VALVE PARAMETERS
INCORRECT

The main lift pvg valves spool data is incorrect. Requires a valve cali-
bration.

TOWER LIFT PVG VALVE PARAMETERS
INCORRECT

The tower lift pvg valves spool data is incorrect. Requires a valve cali-
bration.

TOWER TELESCOPE PVG VALVE PARAM-
ETERS INCORRECT

The tower telescope pvg valves spool data is incorrect. Requires a
valve calibration.

MAIN LIFT PVG VALVE LOCATION
IMPROPER

Main lift pvg valve was hosed wrong or the wiring was incorrect dur-
ing calibration.

TOWER LIFT PVG VALVE LOCATION
IMPROPER

Tower lift pvg valve was hosed wrong or the wiring was incorrect
during calibration.

TOWER TELESCOPE PVG VALVE LOCA-
TION IMPROPER

Tower telescope pvg valve was hosed wrong or the wiring was incor-
rect during calibration.

MAIN LIFT PVG VALVE WIRING INCOR-
RECT

The power wire for the main lift pvg valve is not wired to that valve.

TOWER LIFT PVG VALVE WIRING INCOR-
RECT

The power wire for the tower lift pvg valve is not wired to that valve.

TOWER TELESCOPE PVG VALVE WIRING
INCORRECT

The power wire for the tower telescope pvg valve is not wired to that
valve.

Table 6-9. Help Fault Codes, Displayed Faults, and Descriptions

Fault Flash

Code

Analyzer Display

Description

Priority