Gas Tracer Operator’s Manual

Using Maintenance Mode • 157

Turning the Bump Test Function On or Off

The BUMP DSP menu item is used to turn the bump test function on
or off. If set to OFF, the BUMP menu item in Calibration Mode and
Maintenance Mode does not appear. In addition, the BUMP--SET, BP
INTVL, BP RMNDR,

and BP EXPRD menu items will not display in

Maintenance Mode. The factory setting is OFF.

1. Use the AIR▲ or (SHIFT)▼ buttons to display the BUMP DSP

menu item.

2. Press and release the POWER ENTER button. The screen will

indicate the current setting.

3. Use the AIR▲ or (SHIFT)▼ button to display the desired setting.

4. Press and release the POWER ENTER button to save the setting

and return to the main menu.

Turning the Pump Off Screen On or Off

The POFF DSP menu item is used to turn the Pump Off Screen on or
off. When set to ON, the Pump Off Screen appears in Display Mode
and the user can turn off the pump in order to conserve battery power.
If set to OFF (factory setting), the Pump Off Screen does not appear in
Display Mode and the user cannot turn the pump off.

WARNING: The Gas Tracer is not a gas monitoring device if the

pump is turned off.


MAINTENANCE

BUMP DSP

On


MAINTENANCE

BUMP DSP