A-2

Supplemental Drive Information

Environment
(continued)

Atmosphere:

Important: Drive must not be installed in an area
where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not going
to be installed for a period of time, it must be stored in
an area where it will not be exposed to a corrosive
atmosphere.

Relative Humidity:

5 to 95% non-condensing

Shock:

15G peak for 11ms duration (± 1.0 ms)

Vibration:

0.152 mm (0.006 in.) displacement, 1G peak

Electrical

Voltage Tolerance:

See

page D-14

for full power and operating range.

Frequency Tolerance:

47-63 Hz.

Input Phases:

Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated current.

Displacement Power Factor:

0.98 across entire speed range

Efficiency:

97.5% at rated amps, nominal line volts

Maximum Short Circuit Rating:

85,000 Amps symmetrical

Actual Short Circuit Rating:

Determined by AIC rating of installed fuse/circuit
breaker.

Control

Method:

Sine coded PWM with programmable carrier
frequency. Ratings apply to all drives (refer to the
Derating Guidelines in the PowerFlex Reference
Manual). The drive can be supplied as 6 pulse or 12
pulse in a configured package.

Carrier Frequency:

2, 3 or 4 kHz. Drive rating based on 2 kHz.

Output Voltage Range:

0 to rated motor voltage

Output Frequency Range:

Standard Control – 0 to 400 Hz.

Frequency Accuracy

Digital Input:
Analog Input:

Within ± 0.01% of set output frequency.
Within ± 0.4% of maximum output frequency.

Frequency Control:

Speed Regulation - w/Slip Compensation
(Volts per Hertz Mode)

0.5% of base speed across 40:1 speed range
40:1 operating range
10 rad/sec bandwidth

Speed Regulation - w/Slip Compensation
(Sensorless Vector Mode)

0.5% of base speed across 80:1 speed range
80:1 operating range
20 rad/sec bandwidth

Selectable Motor Control:

Sensorless Vector with full tuning. Standard V/Hz with
full custom capability.

Stop Modes:

Multiple programmable stop modes including Ramp,
Coast, DC-Brake, Ramp-to-Hold, and S-curve.

Accel/Decel:

Two independently programmable accel and decel
times. Each time may be programmed from 0 - 3600
seconds in 0.1 second increments.

Intermittent Overload:

110% Overload capability for up to 1 minute.
150% Overload capability for up to 3 seconds.

Current Limit Capability:

Proactive Current Limit programmable from 20 to
160% of rated output current. Independently
programmable proportional and integral gain.

Electronic Motor Overload Protection:

Class 10 protection with speed sensitive response.
Investigated by U.L. to comply with N.E.C. Article 430.
U.L. File E59272, volume 12.

Category

Specification