3-12

Programming and Parameters

SPEED

COMMAND

Disc

re

te Spee

ds

100

[Jog Speed]

Sets the output frequency when a jog command is issued.

Default:

Min/Max:
Units:

10.0 Hz

–/+[Maximum Speed]
0.1 Hz

101
102
103
104
105
106
107

[Preset Speed 1]
[Preset Speed 2]
[Preset Speed 3]
[Preset Speed 4]
[Preset Speed 5]
[Preset Speed 6]
[Preset Speed 7]

Provides an internal fixed speed command value. In bipolar mode
direction is commanded by the sign of the reference.

Default:

Min/Max:
Units:

5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz

–/+[Maximum Speed]
0.1 Hz

090

,

093

Speed T

rim

117

[Trim In Select]

Specifies which analog input signal is being used as a trim input.

Default:

Options:

2

“Analog In 2”

See

[Speed Ref A Sel]

090

,

093

118

[Trim Out Select]

Specifies which speed references are to be trimmed.

117

,

119

,

120

119

[Trim Hi]

Scales the upper value of the [Trim In Select] selection when the source
is an analog input.

Default:

Min/Max:
Units:

60.0 Hz

–/+[Maximum Speed]
0.1 Hz

082

,

117

120

[Trim Lo]

Scales the lower value of the [Trim In Select] selection when the source is
an analog input.

Default:

Min/Max:
Units:

0.0 Hz

–/+[Maximum Speed]
0.1 Hz

117

Slip Comp

Important: Parameters in the Slip Comp Group are used to enable and tune the Slip Compensation Regulator. In order
to allow the Slip Compensation Regulator to control drive operation, parameter 080 [Speed Mode] must be set to 1 “Slip
Comp”.

121

[Slip RPM @ FLA]

Sets the amount of compensation to drive output at motor FLA.

If the value of parameter 061 [Autotune] = 3 “Calculate,” changes made to
this parameter will not be accepted.

Default:

Min/Max:
Units:

Based on [Motor NP RPM]

0.0/1200.0 RPM
0.1 RPM

061

,

080

,

122

,

123

122

[Slip Comp Gain]

Sets the response time of slip compensation.

Default:

Min/Max:
Units:

40.0

1.0/100.0
0.1

080

,

121

,

122

123

[Slip RPM Meter]

Displays the present amount of adjustment being applied as slip
compensation.

Default:

Min/Max:
Units:

Read Only

0.0/300.0 RPM
0.1 RPM

080

,

121

,

122

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Trimmed
0 =Not Trimmed
x =Reserved

Bit #

Factory Default Bit Values

Trim Ref A

Trim Ref B