Troubleshooting

4-9

Drive does not respond to changes in speed command.

Motor and/or drive will not accelerate to commanded speed.

Motor operation is unstable.

Drive will not reverse motor direction.

Cause(s)

Indication

Corrective Action

No value is coming from the source
of the command.

LCD HIM
Status Line
indicates “At
Speed” and
output is 0 Hz.

1. If the source is an analog input, check

wiring and use a meter to check for
presence of signal.

2. Check [Commanded Freq] for correct

source.

(See page 3-6)

Incorrect reference source has been
programmed.

None

1. Check [Speed Ref Source] for the source of

the speed reference.

(See page 3-21)

2. Reprogram [Speed Ref A Sel] for correct

source.

(See page 3-11)

Incorrect Reference source is being
selected via remote device or digital
inputs.

None

1. Check [Drive Status 1],

page 3-20

, bits 12

and 13 for unexpected source selections.

2. Check [Dig In Status],

page 3-2

to see if

inputs are selecting an alternate source.

3. Reprogram digital inputs to correct “Speed

Sel x” option.

(See page 3-30)

Cause(s)

Indication

Corrective Action

Acceleration time is excessive.

None

Reprogram [Accel Time x].

(See page 3-15)

Excess load or short acceleration
times force the drive into current
limit, slowing or stopping
acceleration.

None

1. Check [Drive Status 2], bit 10 to see if the

drive is in Current Limit.

(See page 3-20)

2. Remove excess load or reprogram [Accel

Time x].

(See page 3-15)

Speed command source or value is
not as expected.

None

Check for the proper Speed Command using
Steps 1 through 7 above.

Programming is preventing the drive
output from exceeding limiting
values.

None

Check [Maximum Speed]

(See page 3-10)

and

[Maximum Freq]

(See page 3-7)

to assure that

speed is not limited by programming.

Cause(s)

Indication

Corrective Action

Motor data was incorrectly entered
or Autotune was not performed.

None

1. Correctly enter motor nameplate data.

2. Perform “Static” or “Rotate” Autotune

procedure.

(Param #061, page 3-8)

Cause(s)

Indication

Corrective Action

Digital input is not selected for
reversing control.

None

Check [Digital Inx Sel],

page 3-30

. Choose

correct input and program for reversing mode.

Digital input is incorrectly wired.

None

Check input wiring.

(See page 1-25)

Direction mode parameter is
incorrectly programmed.

None

Reprogram [Direction Mode],

page 3-19

for

analog “Bipolar” or digital “Unipolar” control.

Motor wiring is improperly phased
for reverse.

None

Switch two motor leads.

A bipolar analog speed command
input is incorrectly wired or signal is
absent.

None

1. Use meter to check that an analog input

voltage is present.

2. Check wiring.

(See page 1-25)

Positive voltage commands forward direction.
Negative voltage commands reverse direction.