Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual
Page 91
Troubleshooting
4-9
Drive does not respond to changes in speed command.
Motor and/or drive will not accelerate to commanded speed.
Motor operation is unstable.
Drive will not reverse motor direction.
Cause(s)
Indication
Corrective Action
No value is coming from the source
of the command.
LCD HIM
Status Line
indicates “At
Speed” and
output is 0 Hz.
1. If the source is an analog input, check
wiring and use a meter to check for
presence of signal.
2. Check [Commanded Freq] for correct
source.
Incorrect reference source has been
programmed.
None
1. Check [Speed Ref Source] for the source of
the speed reference.
2. Reprogram [Speed Ref A Sel] for correct
source.
Incorrect Reference source is being
selected via remote device or digital
inputs.
None
1. Check [Drive Status 1],
, bits 12
and 13 for unexpected source selections.
2. Check [Dig In Status],
to see if
inputs are selecting an alternate source.
3. Reprogram digital inputs to correct “Speed
Sel x” option.
Cause(s)
Indication
Corrective Action
Acceleration time is excessive.
None
Reprogram [Accel Time x].
Excess load or short acceleration
times force the drive into current
limit, slowing or stopping
acceleration.
None
1. Check [Drive Status 2], bit 10 to see if the
2. Remove excess load or reprogram [Accel
Speed command source or value is
not as expected.
None
Check for the proper Speed Command using
Steps 1 through 7 above.
Programming is preventing the drive
output from exceeding limiting
values.
None
Check [Maximum Speed]
and
[Maximum Freq]
speed is not limited by programming.
Cause(s)
Indication
Corrective Action
Motor data was incorrectly entered
or Autotune was not performed.
None
1. Correctly enter motor nameplate data.
2. Perform “Static” or “Rotate” Autotune
procedure.
Cause(s)
Indication
Corrective Action
Digital input is not selected for
reversing control.
None
Check [Digital Inx Sel],
. Choose
correct input and program for reversing mode.
Digital input is incorrectly wired.
None
Check input wiring.
Direction mode parameter is
incorrectly programmed.
None
for
analog “Bipolar” or digital “Unipolar” control.
Motor wiring is improperly phased
for reverse.
None
Switch two motor leads.
A bipolar analog speed command
input is incorrectly wired or signal is
absent.
None
1. Use meter to check that an analog input
voltage is present.
2. Check wiring.
Positive voltage commands forward direction.
Negative voltage commands reverse direction.