Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual

Page 130

Advertising
background image

F-2

C-Frame LPM15 Drive Wiring Diagram

180508-Q01

20

AC Power
Input Leads

GND

L4

179026

L6

L5

179024

179022

L3

L2

179022

179023

L1

179025

L1N

L2N

L1P

L2P

22501-025-04
6 Places

SCR6

L6P

L3N

L6N

L3P

L4N

L5N

L5P

SCR5

L4P

SCR4

(12-Pulse Configuration)

Reactor

50 uh

2

3

1

179000

4

179012
Laminated Bus Assy

(6-Pulse Configuration)

179027

179034

179036

179035

179031

179038

1

REACTOR

50 uh

2

179039

J2

J3

INVERTER CONTROL

179784

SCR2

SCR1

BOARD OPTION(S)

J1

RIO

DeviceNet

TB1

COMMUNICATIONS INTERFACE

J2

J5

179726

J1

J7

J2

CONTROL ASSEMBLY

180493-A02 - 450HP
180493-A03 - 600HP

SCR3

179785

J5

See DETAIL A for
User Connections

STANDARD I/O OPTION(S)

J2

SCR Gate-
Cathode
S1, S2, S3

SCR Gate-
Cathode
S4, S5, S6

J9

AC Lline Sync

179037

179035

179031

179786

3

Current
Feedback

Gate Kill

179000

4

179040

179033

J10

DC Bus/
Cap Bank
Mid-Point

Temp. Sw./
Fan Power

25 KHz PS

J4

J3

179788

J6

P1

POWER INTERFACE

180505-A01

J1

J11

Main Control
Interface

Gate Driver
Interface

J7

J1

ControlNet-Coax
ControlNet-Fiber

RS485, DF-1

RS485, HVAC

PROFIBUS DPV1

EtherNet/IP

Interbus

LonWorks

N/A

OPTIONAL

24V DC - 180524-A01

120V AC - 180525-A01

NO I/O

179864-Q02

179865-Q02

194706-Q02

OPTIONAL

Jumper
180497-Q01

COMMUNICATION

Fan

179196

Fan

179196

P3 P4

180527-Q01

P2

NOTES:

1.) Symbol designates PIN 1 location of connectors.

2.) For S6 hookup: L1 is connected to L4.

L2 is connected to L5.

L3 is connected to L6.

3.) For S12 hookup: AC power is attached individually to L1 thru L6.

Advertising