Monitor file, Monitor file -6 – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual

Page 54

Advertising
background image

3-6

Programming and Parameters

Monitor File

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

MO

NIT

O

R

Me

te

ring

001

[Output Freq]

Output frequency present at T1, T2 & T3 (U, V & W).

Default:

Min/Max:
Units:

Read Only

–/+[Maximum Freq]
0.1 Hz

002

[Commanded Freq]

Value of the active frequency command.

Default:

Min/Max:
Units:

Read Only

–/+[Maximum Speed]
0.1 Hz

003

[Output Current]

The total output current present at T1, T2 & T3 (U, V & W).

Default:

Min/Max:
Units:

Read Only

0.0/Drive Rated Amps

× 2

0.1 Amps

004

[Torque Current]

Based on the motor, the amount of current that is in phase with the
fundamental voltage component.

Default:

Min/Max:
Units:

Read Only

Drive Rating

× –2/+2

0.1 Amps

005

[Flux Current]

Amount of current that is out of phase with the fundamental voltage
component.

Default:

Min/Max:
Units:

Read Only

Drive Rating

× –2/+2

0.1 Amps

006

[Output Voltage]

Output voltage present at terminals T1, T2 & T3 (U, V & W).

Default:

Min/Max:
Units:

Read Only

0.0/Drive Rated Volts
0.1 VAC

007

[Output Power]

Output power present at T1, T2 & T3 (U, V & W).

Default:

Min/Max:
Units:

Read Only

0.0/Drive Rated kW

× 2

0.1 kW

008

[Output Powr Fctr]

Output power factor.

Default:

Min/Max:
Units:

Read Only

0.00/1.00
0.01

009

[Elapsed MWh]

Accumulated output energy of the drive.

Default:

Min/Max:
Units:

Read Only

0.0/214748364.0 MWh
0.1 MWh

010

[Elapsed Run Time]

Accumulated time drive is outputting power.

Default:

Min/Max:
Units:

Read Only

0.0/429496729.5 Hrs
0.1 Hrs

011

[MOP Frequency]

Value of the signal at MOP (Motor Operated Potentiometer).

Default:

Min/Max:
Units:

Read Only

–/+[Maximum Freq]
0.1 Hz

012

[DC Bus Voltage]

Present DC bus voltage level.

Default:

Min/Max:
Units:

Read Only

0.0/Based on Drive Rating
0.1 VDC

013

[DC Bus Memory]

6 minute average of DC bus voltage level.

Default:

Min/Max:
Units:

Read Only

0.0/Based on Drive Rating
0.1 VDC

016
017

[Analog In1 Value]
[Analog In2 Value]

Value of the signal at the analog inputs.

Default:

Min/Max:

Units:

Read Only

0.000/20.000 mA
–/+10.000V
0.001 mA
0.001 Volt

Drive Data

026

[Rated kW]

Drive power rating.

Default:

Min/Max:
Units:

Read Only

0.00/3000.00 kW
0.01 kW

027

[Rated Volts]

The drive input voltage class (208, 240, 400, etc.).

Default:

Min/Max:
Units:

Read Only

0.0/6553.5 VAC
0.1 VAC

028

[Rated Amps]

The drive rated output current.

Default:

Min/Max:
Units:

Read Only

0.0/6553.5 Amps
0.1 Amps

029

[Control SW Ver]

Main Control Board software version.

Default:

Min/Max:
Units:

Read Only

0.000/256.256
0.001

196

32

32

32

Advertising