Chapter 1, Installation/wiring, Power ratings – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual

Page 13: Power ratings -1, Chapter

Advertising
background image

Chapter

1

Installation/Wiring

This chapter provides information on mounting and wiring the LPM15 Drive.

Most start-up difficulties are the result of incorrect wiring. Every precaution
must be taken to assure that the wiring is done as instructed. All items must
be read and understood before the actual installation begins.

Power Ratings

LPM15 Drives have power ratings as described in

Table 1.A

below:

For information on…

See page…

Power Ratings

1-1

Enclosure Ratings

1-2

B-Frame LPM15 Drive Component Locations

1-2

C-Frame LPM15 Drive Component Locations

1-4

D-Frame LPM15 Drive Component Locations

1-6

AC Supply Source Considerations

1-12

Fuses and Circuit Breakers

1-13

Mounting the Drive, Determining Wire Routing, and Grounding

1-13

Coolant Considerations

1-16

Installing Input Power Wiring

1-19

Installing Output Power Wiring

1-22

Power Wiring

1-23

Using Input/Output Contactors

1-24

I/O Wiring

1-24

Reference Control

1-28

Auto/Manual Examples

1-29

CE Compliance

1-30

!

ATTENTION: The following information is merely a guide
for proper installation. The Allen-Bradley Company cannot
assume responsibility for the compliance or the noncompliance
to any code, national, local or otherwise for the proper
installation of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if codes are
ignored during installation.

Table 1.A Power Ratings

(1)

Catalog Number
(positions 1-7 only)

Frame Size

Input
Power (KVA)

Input
Current (Amps)

Output Current
at 2 kHz

(2)

(Amps)

HP Ratings

Full Load Power Loss Watts
Fluid/Air

20MD414

B-Frame

344

414

414

350

4600/1100

20MD500

C-Frame

398

500

500

450

5500/1500

20MD643

C-Frame

512

643

643

600

7000/2000

20MD1K2

D-Frame

956

1200

1200

1000

11700/4000

(1)

110% output current capability for one minute, 150% output current capability for 5 seconds.

(2)

Note that LPM15 drives are rated for use with water at specified temperatures and pressures as the coolant. Some coolant fluids may allow an increased output rating
while others may require the output to be derated. LPM15 drives are also capable of running at 3 kHz or 4 kHz at reduced output.

Advertising