Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual
Page 62
3-14
Programming and Parameters
SPEED
C
O
MMAND
Pr
oc
ess PI
133
[PI Preload]
Sets the value used to preload the integral component on start or enable.
Default:
Min/Max:
Units:
0.0 Hz
–/+400.0 Hz
0.1 Hz
124
thru
138
134
[PI Status]
Status of the Process PI regulator.
Read Only
124
thru
138
135
[PI Ref Meter]
Present value of the PI reference signal.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
124
thru
138
136
[PI Fdback Meter]
Present value of the PI feedback signal.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
124
thru
138
137
[PI Error Meter]
Present value of the PI error.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
124
thru
138
138
[PI Output Meter]
Present value of the PI output.
Default:
Min/Max:
Units:
Read Only
–/+100.0 Hz
0.1 Hz
124
thru
138
Fil
e
Gr
oup
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Related
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Condition True
0 =Condition False
x =Reserved
Bit #
PI Enab
led
PI Hold
PI Reset
PI InLimit