Start Up

2-3

Start-Up Routines

The LPM15 is designed so that start up is simple and efficient. If you have
an LCD HIM, two start-up methods are provided, allowing the user to select
the desired level needed for the application.

S.M.A.R.T. Start

This routine allows you to quickly set up the drive by programming
values for the most commonly used functions. See

page 2-4

.

Assisted Start Up

This routine prompts you for information that is needed to start up a
drive for most applications, such as line and motor data, commonly
adjusted parameters and I/O. See

page 2-4

.

Figure 2.2 Standard Control Option Start Up Menu

Important Information

Power must be applied to the drive when viewing or changing parameters.
Previous programming may affect the drive status and operation when
power is applied.

Configure for

Alternate Input

Voltage

Input Voltage

Start-Up

Enter Motor NP

Data, Stop Mode,

Accel/Decel

Ramp Times

Motor Data and

Ramp Times

Optimize Torque

and

Verify Direction

Motor Tests

Set Min/Max

Speed and

Direction Control

Speed Limits

Configure

Source, Value

and Scale for

Speed References

Speed Control

Start/Stop/I/O

Configure

Control Method

(2 Wire/3 Wire), I/O,

Digital Inputs/Outputs

and Analog Outputs

Done /
Exit

Main Menu:

(1)

(1)

During Motor Tests and tuning procedures, the drive may modify certain parameter values for proper Start Up operation.
These values are then reset to their original values when Start Up is complete. The affected parameters are: 053, 080,
276, 278, and 361-366. If power is removed from the drive during the tests without aborting the auto-tune procedure,
these parameters may not be reset to their original value. If this situation occurs, reset the drive to factory defaults and
repeat the Start Up procedure.