Installation/Wiring

I/O Terminal Blocks

Table 1.H I/O Terminal Block Specifications

Figure 1.11 Control Option I/O Terminal Designations

Name

Description

Wire Size Range

(1)

(1)

Maximum/minimum that the terminal block will accept - these are not recommendations.

Torque

Maximum

Minimum Maximum

Recommended

I/O Terminal
Block

Signal and control
connections

2.1 mm

2

(14 AWG)

0.30 mm

2

(22 AWG)

0.6 N-m
(5.2 lb.-in.)

0.6 N-m
(5.2 lb.-in.)

Standard
Control
Option

No.

Signal

Factory
Default

Description

Related
Param.

1

Anlg Volts In 1 (–)

(2)

(2)

These inputs/outputs are dependant on a number of parameters. See “Related Parameters.”

Isolated

(3)

, bipolar, differential, ± 10V, 11 bit & sign, 88k ohm input

impedance.

(3)

Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.

320 - 327

2

Anlg Volts In 1 (+)

3

Anlg Volts In 2 (–)

(2)

Isolated

(4)

, bipolar, differential, ±10V, 11 bit & sign, 88k ohm input

impedance.

(4)

Differential Isolation - External source must be less than 10V with respect to PE.

4

Anlg Volts In 2 (+)

5

Pot Common

For (+) and (–) 10V pot references.

6

Anlg Volts Out 1 (–)

(2)

Bipolar, ±10V, 11 bit & sign, 2k ohm minimum load.

340 - 344

7

Anlg Volts Out 1 (+)

8

Anlg Current Out 1 (–)

(2)

4-20 mA, 11 bit & sign, 400 ohm maximum load.

9

Anlg Current Out 1 (+)

10

Reserved for Future Use

11

Digital Out 1 – N.C.

(1)

(1)

Contacts in unpowered state. Any relay programmed as Fault or Alarm will energize (pick up) when power is applied to drive and deenergize (drop out) when a fault
or alarm exists. Relays selected for other functions will energize only when that condition exists and will deenergize when condition is removed.

Fault

Max. Resistive Load: 240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10 mA

Max. Inductive Load: 240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA

380 - 387

12

Digital Out 1 Common

13

Digital Out 1 – N.O.

(1)

NOT Fault

14

Digital Out 2 – N.C.

(1)

NOT Run

15

Digital Out 2 Common

16

Digital Out 2 – N.O.

(1)

Run

17

Anlg Current In 1 (–)

(2)

Isolated

(3)

, 4-20 mA, 11 bit & sign, 124 ohm input impedance.

320 - 327

18

Anlg Current In 1 (+)

19

Anlg Current In 2 (–)

(2)

Isolated

(4)

, 4-20 mA, 11 bit & sign, 124 ohm input impedance.

20

Anlg Current In 2 (+)

21

–10V Pot Reference

2k ohm minimum.

22

+10V Pot Reference

23

Reserved for Future Use

24

+24VDC

(5)

Drive supplied logic input power.

(5)

(5)

150 mA maximum Load. Not present on 115V versions.

25

Digital In Common

26

24V Common

(5)

Common for internal power supply.

27

Digital In 1

Stop - CF

115V AC, 50/60 Hz - Opto isolated Low State: less than 30V AC
High State: greater than 100V AC

24V AC/DC, 50/60 Hz-Opto isolated Low State: less than 5V AC/DC
High State: greater than 20V AC/DC, 11.2 mA DC

361 - 366

28

Digital In 2

Start

29

Digital In 3

Jog

30

Digital In 4

Speed Sel 1

31

Digital In 5

Speed Sel 2

32

Digital In 6

Speed Sel 3

1

16

32