Programming and Parameters

3-7

Motor Control File

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

MO

T

O

R C

O

NTR

O

L

Motor D

ata

040

[Motor Type]

Set to match the type of motor connected.

(1)

Important: Selecting option 1 or 2 also requires selection of “Custom
V/Hz,” option 2 in parameter 53.

Default:

Options:

0

0
1
2

“Induction”

“Induction”
“Synchr Reluc”

(1)

“Synchr PM”

(1)

053

041

[Motor NP Volts]

Set to the motor nameplate rated volts.

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Rated Volts]
0.1 VAC

042

[Motor NP FLA]

Set to the motor nameplate rated full load amps.

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Rated Amps]

× 2

0.1 Amps

047

,

048

043

[Motor NP Hertz]

Set to the motor nameplate rated frequency.

Default:

Min/Max:
Units:

Based on Drive Cat. No.

5.0/400.0 Hz
0.1 Hz

044

[Motor NP RPM]

Set to the motor nameplate rated RPM.

Default:

Min/Max:
Units:

1750 RPM

60/2400 RPM
1 RPM

045

[Motor NP Power]

Set to the motor nameplate rated power.

Default:

Min/Max:
Units:

Based on Drive Rating

0.00/100.00
0.01 kW/HP
See

[Mtr NP Pwr Units]

046

046

[Mtr NP Pwr Units]

Selects the motor power units to be used.

Default:

Options:

0
1

Drive Rating Based

“Horsepower”
“kiloWatts”

047

[Motor OL Hertz]

Selects the output frequency below which the motor operating current is
derated. The motor thermal overload will generate a fault at lower levels
of current.

Default:

Min/Max:
Units:

Motor NP Hz/3

0.0/Motor NP Hz
0.1 Hz

042

,

220

048

[Motor OL Factor]

Sets the operating level for the motor overload.

Default:

Min/Max:
Units:

1.00

0.20/2.00
0.01

042

,

220

To

rq

Attrib

utes

053

[Torque Perf Mode]

Sets the method of motor torque production.

Default:

Options:

0

0
1
2
3

“Sensrls Vect”

“Sensrls Vect”
“SV Economize”
“Custom V/Hz”
“Fan/Pmp V/Hz”

054

[Maximum Voltage]

Sets the highest voltage the drive will output.

Default:

Min/Max:
Units:

Drive Rated Volts

Rated Volts x 0.25/Rated Volts
0.1 VAC

055

[Maximum Freq]

Sets the highest frequency the drive will output. Refer to parameter 083
[Overspeed Limit].

Default:

Min/Max:
Units:

110.0 or 130.0 Hz

5.0/420.0 Hz
0.1 Hz

083

056

[Compensation]

Enables/disables correction options.

32

Motor FLA x OL Factor = Operating Level

1

0

x

x

x

x

x

x

x

x

x

x

x

x

x

10

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Enab

le Jerk

Ixo A

utoCalc

Reflected W

ave

0

0