Programming and Parameters

3-13

SPEED C

O

MMA

N

D

Pr

ocess PI

Important: Parameters in the Process PI Group are used to enable and tune the PI Loop. In order to allow the PI Loop
to control drive operation, parameter 080 [Speed Mode] must be set to 2 “Process PI”.

124

[PI Configuration]

Sets configuration of the PI regulator.

124

thru

138

125

[PI Control]

Controls the PI regulator.

080

126

[PI Reference Sel]

Selects the source of the PI reference.

Default:

Options:

0

0
1
2
3-8
9
10
11-17
18-22

“PI Setpoint”

“PI Setpoint”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Master Ref”
“Preset Spd1-7”
“DPI Port 1-5”

124

thru

138

127

[PI Setpoint]

Provides an internal fixed value for process setpoint when [PI Reference
Sel] is set to “PI Setpoint.”

Default:

Min/Max:
Units:

50.00%

–/+100.00% of Max. Process Value
0.01%

124

thru

138

128

[PI Feedback Sel]

Selects the source of the PI feedback.

Default:

Options:

2

“Analog In 2”

See

[PI Reference Sel]

.

124

thru

138

129

[PI Integral Time]

Time required for the integral component to reach 100% of [PI Error
Meter]. Not functional when the PI Hold bit of [PI Control] = “1” (enabled).

Default:

Min/Max:
Units:

2.0 Secs

0.00/100.00 Secs
0.01 Secs

124

thru

138

130

[PI Prop Gain]

Sets the value for the PI proportional component.
PI Error x PI Prop Gain = PI Output

Default:

Min/Max:
Units:

1.0

0.00/100.00
0.01

124

thru

138

131

[PI Lower Limit]

Sets the lower limit of the PI output.

Default:

Min/Max:
Units:

–[Maximum Freq]

–/+400.0 Hz
0.1 Hz

124

thru

138

132

[PI Upper Limit]

Sets the upper limit of the PI output.

Default:

Min/Max:
Units:

+[Maximum Freq]

–/+400.0 Hz
0.1 Hz

124

thru

138

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

0

0

0

0

0

0

0

0

x x x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Exc

l Mode

In

ver

t Err

or

Preload Mode

Ramp Ref

Zer

o Clamp

Feedbak Sqr

t

Stop Mode

Anti-Wind Up

0

0

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

PI Enab

le

PI Hold

PI Reset