Applying Power to the Drive

4. Apply AC power and control voltages to the drive.

If any of the six digital inputs are configured to “Stop – CF” (CF = Clear
Fault) or “Enable,” verify that signals are present or reconfigure [Digital
Inx Sel]. If an I/O option is not installed (i.e. no I/O terminal block),
verify that [Digital Inx Sel] is not configured to “Stop – CF” or “Enable.”
If this is not done, the drive will not start. Refer to

Alarm Descriptions on

page 4-6

for a list of potential digital input conflicts. If a fault code

appears, refer to

Chapter 4

.

If the STATUS LED is not flashing green at this point, refer to LED
Status Definitions in

Table 2.A

.

5. Proceed to Start-Up Routines.

Status Indicators

Figure 2.1 Drive Status Indicator

Table 2.A Ready LED Status Indications

Control Panel

Inverter

Status LED

Color

State

Description

Green

Flashing

Drive ready, but not running and no faults are present.

Steady

Drive running, no faults are present.

Yellow
See

page 4-2

.

Flashing

The drive is not ready. Check parameter 214 [Start Inhibits].

Steady

An alarm condition exists. Check parameters 211 [Drive Alarm 1]
and 212 [Drive Alarm 2].

Red
See

page 4-3

.

Flashing

A fault has occurred.

Steady

A non-resettable fault has occurred.