Programming and Parameters

3-29

INPUTS

&

OUTPUTS

Ana

log Outputs

341

[Anlg Out Absolut]

Selects whether the signed value or absolute value of a parameter is used before being scaled to drive the analog
output.

342

[Analog Out1 Sel]

Selects the source of the value that drives the analog output.

Default:

Options:

0 “Output Freq”

See Table

001

,

002

,

003

,

004

,

005

,

006

,

007

,

012

,

135

,

136

,

137

,

138

,

220

,

219

343

[Analog Out1 Hi]

Sets the analog output value when the source value is at maximum.

Default:

Min/Max:

Units:

20.000 mA, 10.000 Volts

4.000/20.000mA
–/+10.000V
0.000/10.000V
0.001 mA
0.001 Volt

340

,

342

344

[Analog Out1 Lo]

Sets the analog output value when the source value is at minimum.

Default:

Min/Max:

Units:

0.000 mA, 0.000 Volts

4.000/20.000mA
–/+10.000V
0.000/10.000V
0.001 mA
0.001 Volt

340

,

342

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

x x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Absolute
0 =Signed
x =Reserved

Bit #

Factory Default Bit Values

Analog Out1

Options

[Analog Out1 Lo] Value

[Analog Out1 Hi] Value

Param. 341 = Signed

Param. 341 = Absolute

0
1
2
3
4
5
6
7
8
9
10
11
12
13

“Output Freq”
“Command Freq”
“Output Amps”
“Torque Amps”
“Flux Amps”
“Output Power”
“Output Volts”
“DC Bus Volts”
“PI Reference”
“PI Feedback”
“PI Error”
“PI Output”
“%Motor OL”
“%Drive OL”

–[Maximum Speed]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%

0 Hz
0 Hz
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%

+[Maximum Speed]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% Rated
120% Rated Input Volts
200% Rated Input Volts
100%
100%
100%
100%
100%
100%