Selecting Input Line Branch Circuit Fuses

Input line branch circuit protection fuses must be used to protect the input
power lines. See

Figure 1.9

and

Figure 1.10

for typical AC input/output

connection diagrams. Recommended fuse values are shown in

Table 1.C

.

The listed input fuse ratings are applicable for one drive per branch circuit.
No other load may be applied to that fused circuit.

Table 1.C AC Input Line Fuse and Circuit Breaker Selection Values

Fuses and Circuit Breakers

The LPM15 can be installed with either input fuses or an input circuit
breaker. National and local industrial safety regulations and/or electrical
codes may determine additional requirements for these installations. Refer
to

Table 1.C

for recommended fuses/circuit breakers.

Mounting the Drive,
Determining Wire Routing,
and Grounding

This chapter shows how to mount the drive and properly ground it. Also
described is the wiring to be routed in and out of the drive.

Lifting and Mounting the Drive

Use the following procedure to lift the LPM15 drive and mount it in the
required enclosure:

!

ATTENTION: Most codes require that upstream branch circuit
protection be provided to protect input power wiring. Install the
fuses recommended in

Table 1.C

. Do not exceed the fuse

ratings. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.

LPM15 Drive
Catalog Number
(positions 1-7 only)

Input Voltage
(+/-10%)

Fuse Rating

Motor Circuit Protector
or Circuit Breaker

20MD414

380-480 VAC

600 A

(1)

(1)

Recommended fuse type: UL Class J, 600 V, time-delay, or equivalent.

600 A

20MD500

380-480 VAC

750 A

(2)

(2)

Recommended fuse type: UL Class L, 600 V, time-delay, or equivalent.

800 A

20MD643

380-480 VAC

1000 A

(1)

1000 A

20MD1K2

380-480 VAC

1600 A

(2)

1500 A

!

ATTENTION: The LPM15 does not provide branch short
circuit protection. Specifications for the recommended fuse or
circuit breaker to provide protection against short circuits are
provided in

Table 1.C

.