Drive Status

The condition or state of your drive is constantly monitored. Any changes
will be indicated by the INV. STATUS LED on the DPI Communication
Interface Board and/or the HIM (if present).

Front Panel LED Indications

Figure 4.1 Typical Inv. Status LED Indications

HIM Indication

The LCD HIM also provides visual notification of a fault or alarm condition.

DPI Port 3

INV. STATUS

Rockwell Automation

Color

State

Description

Green

Flashing

Drive ready, but not running & no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing

A Type 2 (non-configurable) alarm condition exists, drive continues to run.

Steady

A Type 1 (user configurable) alarm condition exists, but drive continues to run.

Red

Flashing

A fault has occurred. Check [Fault x Code] or Fault Queue.

Steady

A non-resettable fault has occurred.

Condition

Display

Drive is indicating a fault.

The LCD HIM immediately reports the fault condition by displaying the
following:

•“Faulted” appears in the status line
•Fault number
•Fault name
•Time that has passed since fault occurred

Press Esc to regain HIM control.
Drive is indicating an alarm.

The LCD HIM immediately reports the alarm condition by displaying
the following:

•Alarm name (Type 2 alarms only)
•Alarm bell graphic

F-> Faulted

Auto

0.0

Hz

Main Menu:
Diagnostics
Parameter

— Fault — F

5

OverVoltage
Time Since Fault

0000:23:52

F-> Power Loss

Auto

0.0

Hz

Main Menu:
Diagnostics
Parameter
Device Select