4-4

Troubleshooting

Hardware Fault

130

Gate array load error.

1. Cycle power.

2. Replace Main Control Board.

Hardware Fault

131

Dual port failure.

1. Cycle power.

2. Replace Main Control Board.

Heatsink OvrTemp

8

Heatsink temperature exceeds 100% of [Drive Temp]. 1. Verify that maximum ambient temperature has not

been exceeded.

2. Check fan.

3. Check for excess load.

HW OverCurrent

12

The drive output current has exceeded the hardware
current limit.

Check programming. Check for excess load, improper
DC boost setting, DC brake volts set too high or other
causes of excess current.

Incompat MCB-PB

106

Drive rating information stored on the power board is
incompatible with the main control board.

Load compatible version files into drive.

I/O Comm Loss

121

I/O Board lost communications with the Main Control
Board.

Check connector. Check for induced noise. Replace
I/O board or Main Control Board.

I/O Failure

122

I/O was detected, but failed the powerup sequence.
I/O Board is separate in Standard Control.

Replace I/O Board (Standard Control).

IR Volts Range

77

“Calculate” is the autotune default and the value
determined by the autotune procedure for IR Drop
Volts is not in the range of acceptable values.

Re-enter motor nameplate data.

IXo VoltageRange

87

Voltage calculated for motor inductive impedance
exceeds 25% of [Motor NP Volts].

1. Check for proper motor sizing.

2. Check for correct programming of [Motor NP Volts],

parameter 41.

3. Additional output impedance may be required.

Motor Overload

7

➀ ➂

Internal electronic overload trip. Enable/Disable with
[Fault Config 1] on

page 3-23

.

An excessive motor load exists. Reduce load so drive
output current does not exceed the current set by
[Motor NP FLA].

NVS I/O Checksum

109

EEprom checksum error.

1. Cycle power and repeat function.

2. Replace Main Control Board.

NVS I/O Failure

110

EEprom I/O error.

1. Cycle power and repeat function.

2. Replace Main Control Board.

OverSpeed Limit

25

Functions such as Slip Compensation or Bus
Regulation have attempted to add an output
frequency adjustment greater than that programmed
in [Overspeed Limit].

Remove excessive load or overhauling conditions or
increase [Overspeed Limit].

OverVoltage

5

DC bus voltage exceeded maximum value.

Monitor the AC line for high line voltage or transient
conditions. Bus overvoltage can also be caused by
motor regeneration. Extend the decel time or install
dynamic brake option.

Parameter Chksum

100

The checksum read from the board does not match
the checksum calculated.

1. Restore defaults.

2. Reload User Set if used.

Params Defaulted

48

The drive was commanded to write default values to
EEPROM.

1. Clear the fault or cycle power to the drive.

2. Program the drive parameters as needed.

Phase U to Grnd

38

A phase to ground fault has been detected between
the drive and motor in this phase.

1. Check the wiring between the drive and motor.

2. Check motor for grounded phase.

3. Replace drive.

Phase V to Grnd

39

Phase W to Grnd

40

Phase UV Short

41

Excessive current has been detected between these
two output terminals.

1. Check the motor and drive output terminal wiring

for a shorted condition.

2. Replace drive.

Phase VW Short

42

Phase UW Short

43

Table 4.A Fault Types, Descriptions and Actions (Continued)

Fault

No.

Type

(1)

Description

Action