Programming and Parameters

3-17

D

Y

NA

MA

NIC CO

NTR

O

L

Restar

t Modes

178

[Sleep-Wake Mode]

Enables/disables the Sleep/Wake function. Important: When enabled,
the following conditions must be met:
• A proper minimum value must be programmed for [Sleep Level].
• A speed reference must be selected in [Speed Ref A Sel].
• At least one of the following must be programmed (and input closed) in

[Digital Inx Sel]; “Enable,” “Stop=CF,” “Run,” “Run Forward,” “Run
Reverse.”

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Direct” (Enabled)

179

[Sleep-Wake Ref]

Selects the source of the input controlling the Sleep-Wake function.

Default:

Options:

2

1
2

“Analog In 2”

“Analog In 1”
“Analog In 2”

180

[Wake Level]

Defines the analog input level that will start the drive.

Default:

Min/Max:

Units:

6.000 mA, 6.000 Volts

[Sleep Level]/20.000 mA
[Sleep Level]/10.000 Volts
0.001 mA
0.001 Volts

181

181

[Wake Time]

Defines the amount of time at or above [Wake Level] before a Start is
issued.

Default:

Min/Max:
Units:

1.0 Secs

0.0/30.0 Secs
0.1 Secs

180

182

[Sleep Level]

Defines the analog input level that will stop the drive.

Default:

Min/Max:

Units:

5.000 mA, 5.000 Volts

4.000 mA/[Wake Level]
0.000 Volts/[Wake Level]
0.001 mA
0.001 Volts

183

183

[Sleep Time]

Defines the amount of time at or below [Sleep Level] before a Stop is
issued.

Default:

Min/Max:
Units:

1.0 Secs

0.0/30.0 Secs
0.1 Secs

182

Fil

e

Gr

oup

No.

Parameter Name & Description

See

page 3-2

for symbol descriptions

Values

Related

!

ATTENTION: Enabling the Sleep-Wake function can cause unexpected machine operation during the
Wake mode. Equipment damage and/or personal injury may result if this parameter is used in an
inappropriate application. Do not use this function without considering applicable local, national, and
international codes, standards, regulations or industry guidelines.

Conditions Required to Start Drive

(1)

(2)

(3)

(1)

When power is cycled, if all conditions are present after power is restored, restart will occur.

(2)

If all conditions are present when [Sleep-Wake Mode] is “enabled,” the drive will start.

(3)

The active speed reference is determined as explained in

Reference Control on page 1-28

. The Sleep/Wake

function and the speed reference may be assigned to the same input.

Input

After Power-Up

After a Drive Fault

After a Stop Command

Reset by Stop-CF, HIM or TB

Reset by Clear Faults (TB)

HIM or TB

Stop

Stop Closed
Wake Signal

Stop Closed
Wake Signal
New Start or Run Cmd.

(4)

(4)

Command must be issued from HIM, TB or network.

Stop Closed
Wake Signal

Stop Closed
Analog Sig. > Sleep Level

(6)

New Start or Run Cmd.

(4)

Enable

Enable Closed
Wake Signal

(4)

Enable Closed
Wake Signal
New Start or Run Cmd.

(4)

Enable Closed
Wake Signal

Enable Closed
Analog Sig. > Sleep Level

(6)

New Start or Run Cmd.

(4)

Run
Run Forward
Run Reverse

Run Closed
Wake Signal

New Run Cmd.

(5)

Wake Signal

Run Closed
Wake Signal

New Run Cmd.

(5)

Wake Signal

(5)

Run Command must be cycled.